Main technical parameters
1、Ground Impedance
Output test voltage: 0~60V;
Output current: 0~300mA;
Frequency adjustment range: 40~500Hz;
Resolution: 1mΩ;
Measurement range: 0.001~299.9Ω;
2Soil resistivity: Testing method: Quadrupole equidistant method;
3. Equipotential, transition resistance, and conductivity tests:
Test electricityflow:0.2~2A continuously adjustable, with a step value of 0.1A;
resolving power:1mΩ;
Measurement accuracy:200mΩ±1% 20Ω±2%
Measurement radius:0~100 meters;
4Display mode:7-inch high-definition color touch screen display;
5Data storage:USB drive;
6work environment:temperature-10℃~+50℃ humidity≤90%Altitude≤2000m;
7Working power supply:12V dedicated lithium iron phosphate battery power supply;
8shapeSize:323x 275x 135 mm.