XO-KB2200 gas alarm host
XO-KB2200 gas alarm host
Product details

XO-KB2200 gas alarm host

Product Features:

Embedded real-time operating system, equipped with feature rich application software, completes transmitter signal sampling, filtering, calculation, system fault detection, key scanning, display driver, various alarm display and alarm control functions

4-20mA standard analog output, compatible with DCS and PLC systems

4-channel relay electrical passive switch output can be used as a trigger signal for external devices or as a direct drive for external devices. Each relay can be individually set, making it flexible and convenient to apply

Can manage detectors that detect different gas types, ranges, and data units

Dual power input, both 220VAC and 24DC can supply power

Color LCD display, Chinese interactive interface, more convenient operation

Independent units can be freely combined and combined with various gas detectors

Performance indicators:

Installation method: Cabinet style installation

Compatible detectors: XO20H series, XO21N series, XO109C series

Concentration units:% LEL, ppm,% VOL

Measurement accuracy: ± 5% F.S

Response time: ≤ 10s

Indication method: Color LCD displays real-time data and system status

LED indicates alarm or fault status

Sound prompt alarm and malfunction

Contact output: Passive contact capacity 2A/AC220V

Working mode: Continuous work

Environmental conditions: Temperature -10 ℃~50 ℃ Humidity ≤ 95% RH

Main power supply: AC220V ± 15%, 50Hz ± 1%, or DC24V+25%

Power: ≤ 10W

Detector power supply voltage: DC24V ± 25%

Header dimensions: 43mm × 180mm × 117mm

Overall dimensions of the machine: 495mm × 3000mm × 178mm

The current requirement for the connection between the detector and the host is ≥ RVVP 3 × 1.5mm2

Communication distance between detector and host: ≤ 1000m