XO-AC2011D Combustible Gas Alarm Host
Product Features:
Dual HBUS four bus communication interface with automatic protection function to prevent damage to the controller caused by any short circuit of the circuit during construction or use.
Adopting LCD liquid crystal display and a fully Chinese graphical operation interface, it has three display modes: list, curve, and column, and can simultaneously monitor gases in units of% LEL, ppm, and% VOL.
Adopting an ARM and AVR dual processor design architecture, it responds faster and runs more stably.
Automatic calibration and tracking of sensor aging status; Automatic fault monitoring function, which can indicate the location and type of the fault.
Remote sensitivity correction and zero point adjustment of detectors can be performed without the need for on-site calibration using large gas distribution equipment.
Built in large capacity data storage, capable of classifying and storing fault records, alarm records, power on/off records, and event records, without loss during power outages.
Anti RFI/EMI interference.
Can be used for the renovation of three wire split line equipment.
Provide two multifunctional output communication interfaces (COM1, COM2), which can realize controller interconnection, TCP/IP interface, communication with the upper computer, and connection to micro printers.
Fully modular system design, convenient for debugging and maintenance of large systems.
Optional power supply with seamless switching between main and backup power and working status indication function.
Technical Indicators:
Working voltage: AC220V ± 15%/50Hz
Capacity: The number of detectors and input modules shall not exceed 512,
Scalable output modules not exceeding 512
Indication units:% LEL, ppm,% VOL
Power consumption: ≤ 50W
Signal transmission: HBUS quad bus
Signal transmission distance: ≤ 1500mm (2.5mm)2×2)
Output: 4 sets of programmable outputs,
Contact capacity 2A/DC24V or 1A/AC220V
Alarm method: Sound and light alarm
Alarm volume: ≥ 65dB
Display mode: graphical Chinese LCD display
Operating environment: Temperature range of 0 ℃ to 40 ℃,
Relative humidity<93% RH (no condensation)
Dimensions: 520mm × 410mm × 125mm (cabinet machine can be customized)
Installation method: Wall mounted
Whole machine weight: 16kg
Optional: DC12V/4Ah × 2 backup power supply