1、 Product features:
l High reliability. International first instrument power supply85V-264VTo provide assurance for long-term use of instruments, especially suitable for unstable power grids and diesel engine power generation systems.
l Input signalK、E、J、S、T、B、PT100, can be freely configured,0~10V、0~5V、4~20mAWaiting for various standard signals.
l Output:SSR、RLY、SSC、0-10V、4-20mAWait.
l Equipped with input signal filtering function (filter coefficient)0-100Adjustable)
l Zero position deviation can be adjusted by the user.
l The power output can be limited. (Can suppress instrument overshoot and overshoot)
l call the police:7Various alarm forms can be configured freely.
l Adopting single key operation (easy to operate)
l Instrument size:XMG1:48×48、XMG6:96×48、XMG7:72×72、XMG8:48×96、XMG9:96×96、XMG16:160×80
Please inform when placing an order: instrument size, input signal, output signal, and how many alarms are required.
IIXMG—2500Series and on-site wiring diagram:
3、 Main technical indicators and performance
Indication accuracy |
±0.3%FS±1One word |
Set accuracy |
±0.3%FS±1One word |
Input sampling period |
0.2second |
Relay contact control output |
250VAC3A(Resistive load)250VAC 1A(Sensory load,COSφ=0.4) |
Contactless voltage control output |
(Used for)SSRDrive)12VDC, the largest40mA(Short circuit protection) |
Current and voltage output |
4~20 mA dcLoad resistancemax=500Ohm.0~10VDCLoad current ≤10mA |
External auxiliary power supply(feed) |
10V、12V、24VappointChoose,Load current ≤20mA |
Alarm method |
ONOFFMethod, lag,1℃(1℃)Or0.1℃ |
ALARM IN |
Relay contacts:250VAC3A(Resistive load)250VAC 1A(Sensory load,COSφ=0.4) |
supply voltage |
85~264VAC,50/60Hz.24VAC/DC,50/60Hz |
Voltage variation range |
85~264VAC,22~26VAC/DC |
ambient temperature |
-5~50℃ |
ambient humidity |
80%RH |
weight |
230g |
power consumption |
make an appointment4W |
insulation resistance |
10Mega even (testing conditions)500V) |
4XMG—2500Selection Table for Series Intelligent Digital Display Regulator
type name |
speak bright |
|||||||||
XMG |
opening |
-opening |
-opening |
/opening |
-opening |
-opening |
-opening |
-opening |
-opening |
|
hole size |
9 |
96×96×58mm holesize:91×91mm |
||||||||
8 |
48×96×58mm holesize:43.8×91mm |
|||||||||
7 |
72×72×69mm holesize:66.3×66.3mm |
|||||||||
6 |
96×48×58mm holesize:91×43.8mm |
|||||||||
1 |
48×48×67mm holesize:45.1×45.1mm |
|||||||||
16 |
160×80×69mm holesize:149×75mm |
|||||||||
3 |
rotundity diameter111 mmG3The power supply for the temperature control instrument is24V |
|||||||||
External dimensions |
2500 |
Double four digit numberdisplay |
||||||||
control output |
0 |
not haveoutput |
||||||||
R |
Relay |
|||||||||
S |
Solid state relaySSRoutput |
|||||||||
G1 |
Zero crossing trigger output of thyristor |
|||||||||
I |
electric currentoutput:4~20mA |
|||||||||
V1 |
voltageoutput:0~5V |
|||||||||
V2 |
voltageoutput:0~10V |
|||||||||
B |
Non feedback proportional motor(Gas or natural gas heating) |
|||||||||
B1 |
Feedback proportional motor(Gas or natural gas heating) |
|||||||||
Input signal |
E |
thermocouple,thermal resistance:PT100,K,E,J,S,T,BFree choice |
||||||||
EI1 |
direct-currentelectric current: 4~20mA |
|||||||||
EI2 |
direct-currentelectric current:0~10mA |
|||||||||
EI3 |
direct-currentelectric current:0~20 mA |
|||||||||
EV1 |
direct-currentvoltage:0~5V |
|||||||||
EV2 |
direct-currentvoltage:1~5V |
|||||||||
EV3 |
direct-currentvoltage:0~10V |
|||||||||
call the police1 |
0 |
No alarm |
||||||||
A1 |
The first routecall the police(6Alarm method+coldOutput selectable) |
|||||||||
call the police2 (option) |
0 |
No alarm |
||||||||
A2 |
auxiliary word for ordinal numberstworoadcall the police(6Alarm method+coldOutput selectable) |
|||||||||
Auxiliary power supply(feed)(option) |
0 |
No external power supply |
||||||||
PV1 |
External supply24VDC |
|||||||||
PV2 |
External supply12VDC |
|||||||||
PV3 |
other |
|||||||||
Instrument power supply(switch power supply) |
0 |
220V 50HZAllowable voltage variation range: 185~264V AC |
||||||||
B1 |
110V 50HZAllowable voltage variation range: 85~264V AC |
|||||||||
B2 |
48V AC/DC |
|||||||||
B3 |
24V AC/DC |
Example of selection:XMG9-2500-R/E/A1-A2-0-0
XMG9The external dimensions are96×96mm;2500For the instrument program serial number;ROutput for relay;EFor thermocouples or platinum resistors;
A1Call the first line of alarm;A2Alarm for the second channel (alarm form)7Freely configurable);0For no power supply;0For instrument power supply220VAC.
5、 Wiring terminal diagram: