WP-9000 series thermocouple temperature transmitter (output loop power supply) isolates and converts on-site thermocouple or millivolt signals into DC signals (4-20) mA, which are transmitted to the control system or other unit combination instruments.
Some signal receiving devices come with a 24V power supply. Generally, temperature transmitters output active signals, which may cause power conflicts when connected. Using an output loop power supply type can avoid power conflicts and achieve signal isolation.
Intelligent thermocouple temperature transmitter. Users can configure and set the thermocouple type and range through software.
This temperature transmitter has independent power supply mode and output circuit power supply interface requirements, with electromagnetic isolation between the power supply input circuit output circuit.
◆ Characteristics
Thermocouple temperature transmitter isolated output.
Output current signal (4-20) mA.
Output circuit power supply (12-35) V.
Intelligent, capable of on-site configuration settings. Fixed thermocouple types and temperature range inputs can also be selected.
Modular core design, no need for zero and full adjustment, automatic dynamic calibration of zero and automatic compensation for temperature drift.
Equipped with a working power indicator light.
● Input circuit overcurrent protection.
● Plug and unplug terminal block, DIN rail card installation.
● Working power supply
Power wiring: independent wiring terminals 13-, 14+, can be plugged and unplugged with power on
Power supply voltage: (20-30) VDC
Current loss:<30mA at 24VDC (one in one out)
< 45mA (one in and two out)
Power indicator: Power on LED light on: green
● Input signal
Input thermocouple types: K, E, S, B, R, T, N, W, J and other types of thermocouples
Optional input millivolt signal: (-5~60) mV; Or specify the millivolt voltage range
● Output signal
Output current (Io): (4-20) mA;
Output circuit power supply voltage (Uo): (12-35) V
Voltage drop (Ud): 5V
Allowable load during current output: RL ≤ (Uo Ud)/Io
Ripple (Vp-p): < 10mV
● Performance indicators
Standard accuracy: ± 0.5% FS, ± 0.2% FS
Temperature drift: ± 0.015%/℃
Response time: ≤ 1s (10 → 90)%
Stability time: ≤ 3s
Impact of power supply voltage variation: ± 0.1% (allowable voltage range)
Influence of load resistance change: ± 0.1%/250 Ω
Channel isolation: isolation between input output power supply
Insulation resistance: ≥ 100M Ω/500VDC (AC)
Isolation capability: 1500VAC/1 minute 50Hz
Electromagnetic compatibility: Complies with relevant electromagnetic standards of IEC 61000
● Environmental parameters
Working temperature: (-20~+60) ℃
Storage temperature: (-40~+80) ℃
Environmental humidity: (5~+95)% RH (without condensation)
● Structure
Card mounted type; Modular watch core; ABS material casing; Plug in terminal
Whole machine weight: approximately 110g
◆ External dimensions
Dimensions: Width x Height x Depth=16 x 116 x 110 (mm)