V230Y Self operated (Micro) Differential Pressure Regulating Valve
V230Y Self operated (Micro) Differential Pressure Regulating ValveProduct Overview:
V230Y11/12 type self operated differential (micro) pressure regulating valveIt is an energy-saving product that does not require external energy and utilizes the energy in the process pipelinePressure changes and signalsCompare and balance the force of the regulated medium with the output force of the actuator to achieve a determined pressure and differential pressure value. It is mainly used in various industrial furnace gas combustion systems to control the mixing ratio flow of fuel A and B to achieve ideal combustion conditions. The self operated differential pressure regulating valve can be used in the sealing oil system of steam turbine generators to ensure the normal and safe operation of the generator set and improve power generation efficiency. Can be used forGas, natural gas, liquefied gas, petroleum gas, nitrogen gasReduce pressure and adjust micro pressure of various industrial gases. Self operated differential pressure regulating valve can also be applied toPetroleum, chemical, metallurgical, pharmaceuticalDuring the process of waiting for the industrial sectorDifferential pressure or micro pressure, balance systemAutomatic adjustment.
V230Y Self operated (Micro) Differential Pressure Regulating ValveMain component materials:
Valve body: HT200, ZG230-450, ZG1Cr18Ni9Ti, ZGCr18Ni12MoTi
Valve core: Cr18Ni12Mo2Ti, 1Cr18Ni9Ti
Valve seat: Cr18Ni12Mo2Ti, 1Cr18Ni9Ti
Spring: 60Si12Mn, 1Cr18Ni9Ti, 50CrVA
Bellows: 1Cr18Ni9Ti
Diaphragm: Nitrile rubber, Oil resistant rubber, Fluororubber Diaphragm cover: A3, 1Cr18Ni9Ti
V230Y Self operated (Micro) Differential Pressure Regulating ValveMain technical parameters:
Nominal diameter DN (mm) | 20 | 25 | 32 | 40 | 50 | 65 | 80 | 100 | |
Rated flow coefficient Kv | Single seat | 8 | 11 | 20 | 32 | 50 | 80 | 100 | 160 |
Double seat | 53 | 83 | |||||||
Rated travel L (mm) | 6 | 8 | 10 | 15 | 20 | ||||
Nominal pressure PN (MPa) | 0.10, 1.0 | ||||||||
Differential pressure regulation range (KPa) | 0.5-5.5, 5-10, 9-14, 13-19, 18-24, 22-28, 26-33, 31-38, 36-44, 42-51, 49-58, 56-66, 64-78, 76-90, 88-100 | ||||||||
Medium temperature () | ≤80 | ||||||||
Adjustment accuracy () | ≤10 | ||||||||
Allowable leakage rate (1/h) | Single seat | 10-4 x rated capacity of valve (Class IV) | |||||||
Double seat | 5 x 10-3 x rated capacity of valve (Class II) |
V230Y Self operated (Micro) Differential Pressure Regulating ValveMain overall dimensions
Nominal Diameter | 20 | 25 | 32 | 40 | 50 | 65 | 80 | 100 |
Flange distance (L) | 185 | 200 | 205 | 222 | 254 | 276 | 298 | 352 |
Actuator width (K) | 395 | |||||||
Total height (H) | 376 | 465 | 365 | 445 | 445 | 490 | 490 | 510 |
Joint thread | M16χ1.5 | |||||||
Flange standard | GB:1.6、2.5、4.0Mpa ANSI:150、300Lb JIS:10K、20K |
Note: The flange distance in this table is based on PN16
-
ZZYP series self operated (micro) differential pressure regulating valve