Purpose:This machine is suitable for the maintenance and installation of power insulation equipment such as transformers, oil switches, and transformers that are in long-term operation. It is particularly suitable for the regeneration treatment of severely inferior insulation oil and can be used for vacuum oiling and drying of transformers.
Technical parameter table of ZJL series multifunctional oil processing machine
|
indicator name
|
unit
|
ZJL-10
|
ZJL-20
|
ZJL-30
|
ZJL-50
|
ZJL-100
|
ZJL-150
|
ZJL-200
|
|
|
traffic
|
L/min
|
10
|
20
|
30
|
50
|
100
|
150
|
200
|
|
|
工作真空度
|
Mpa
|
-0.08 ~-0.095
|
|||||||
|
work pressure
|
Mpa
|
≤0.3
|
≤0.5
|
||||||
|
Constant temperature control range
|
℃
|
20 ~80
|
|||||||
|
power supply
|
|
380V/50Hz (according to user requirements)
|
|||||||
|
operating noise
|
dB(A)
|
≤75
|
≤75
|
≤75
|
≤75
|
≤80
|
≤80
|
≤80
|
|
|
electric heating power
|
kW
|
9
|
18
|
24
|
30
|
60
|
120
|
150
|
|
|
Total electric power
|
kW
|
10.5
|
21
|
27
|
33
|
65
|
127
|
159
|
|
|
Inlet (outlet) pipe diameter
|
mm
|
25
|
25
|
25
|
32
|
42
|
50
|
50
|
|
|
Equipment weight
|
Kg
|
350
|
450
|
650
|
800
|
1200
|
1650
|
1900
|
|
|
Oil breakdown voltage
|
kV
|
≥65
|
|||||||
|
Water content in oil
|
PPm
|
≤5
|
|||||||
|
Gas content in oil
|
%
|
≤0.1
|
|||||||
|
Particle size containing impurities
|
um
|
≤ 1-5 (no free carbon)
|
|||||||
|
Media loss
|
Tgd
|
≤0.005
|
|||||||
|
interfacial tension
|
MN/m
|
≥40
|
|||||||
Optional modes
1. According to different modes of movement, you can choose from regular, manual, or handheld.
2. According to different environmental requirements, ordinary type, fully enclosed type, and explosion-proof type can be selected.
3. Users can freely choose device colors according to their preferences.