Siemens QFM2160 and QFM2171 air duct temperature and humidity sensors
Siemens room temperature and humidity sensor QFM2160 QFM2171 is used for relative humidity and temperature
Product details
Symaro ™ sensor
Siemens air duct temperature and humidity sensor QFM2160 QFM2171
Used for relative humidity and temperature
• Working voltage AC 24 V or DC 13.5... 35 V
Signal output DC 0... 10 V/4... 20 mA, used for relative humidity
Signal output DC 0... 10 V/4... 20 mA or T1 or LG-Ni 1000, used for temperature
The measurement accuracy is ± 3% relative humidity within the comfortable range
purpose
Siemens QFM2160 QFM2171... Duct type temperature sensor is specifically designed for the following purposes in ventilation and air conditioning equipment:
• Relative humidity and
• Temperature
This sensor has the following purposes:
• Control air supply and exhaust
Reference sensors, such as dew point conversion
• Restricted sensors, such as those connected to steam humidity sensors
• Limiting sensors, such as displaying measurement values or connecting to a building automation system
• Enthalpy and absolute humidity sensors, used in conjunction with AQF61.1 (reference technical data N1899) or SEZ222 (reference technical data N5146)
Model Overview
| Reference model | Temperature measurement range | Temperature signal output | Humidity signal output | Working Voltage |
| QFM2100 | None | None | DC 0...10V | AC 24V or DC 13.5…35V |
| QFM2101 | None | None | 4…20 mA | DC 13,5…35 V |
| QFM2120 | 0..50℃/-35..+35℃/-40...70 °C | LG-Ni 1000 | DC 0...10V | AC 24V or DC 13.5…35V |
| QFM2160 | 0..50℃/-35..+35℃/-40...70 °C | DC 0...10V | DC 0...10V | AC 24V or DC 13.5…35V |
| QFM2171 | 0..50℃/-35..+35℃/-40...70 °C | 4…20 mA | 4…20 mA | DC 13.5…35V |
Ordering and Delivery
When placing an order, please indicate the product name and reference model, for example:
Duct type temperature sensor QFM2120
Install the flange and wire connection sealing tube M16 together with the sensor for supply.
Equipment combination
All systems or devices are capable of acquiring and processing DC 0... 10 V or 4... 20 mA, LG Ni 100 or T1 output signals from sensors.
When using passive temperature sensors for averaging, we recommend using the SEZ220 signal converter (Technical Data N5146)
function
relative humidity
The sensor obtains the relative humidity value inside the air duct by changing the capacitance value of the sensing element as a function of humidity.
The electronic measurement circuit converts the sensor signal into a continuous DC 0-10V signal, corresponding to a relative humidity of 0-100%.
temperature
The sensor obtains the temperature value inside the air duct by changing the resistance value of the sensing element as a function of temperature.
This value is converted into an output signal of DC 0... 10V or 4... 20mA based on different temperature measurement ranges of 0... 50 ° C, -35...+35 ° C, or -40... 70 ° C. The measurement range can be selected.
Mechanical Design
-The air duct temperature sensor includes a housing, printed circuit board, connection terminal, mounting flange, and immersion rod with a measuring device. The modular housing includes a base and a detachable panel (threaded connection). The measurement circuit and setting components are located on the printed circuit board inside the panel, while the connection terminals are on the base.
-The sensing element is located at the end of the measuring device and is protected by a filter cap.
-The wire connection is made by connecting the M16 wire carried by the sensor to the sealed tube (IP 54) and fixing it inside the housing with screws.
-The immersion rod and shell are made of plastic and tightly connected.
-The sensor is installed through the accompanying mounting flange. Insert the flange into the immersion rod and fix it according to the required immersion length.
Component settings
Set the position of the component inside the panel. It includes 6 pins and a short plug. It is used to select the desired temperature measurement range and activate testing functions.

• Used for active temperature measurement range:
Left position short plug (R1)=-35...+35 ° C
Middle position short plug (R2)=0... 50 ° C (factory setting)
Short plug on the right side (R3)=-40... 70 ° C
• Used to activate testing functions:
Short plug in horizontal position: The signal output will display the value of the test function activation.
error
If the temperature sensor malfunctions, after 60 seconds, the temperature signal output terminal U2 (I2) will show 0V (4mA), while the humidity signal output U1 (I1) will reach 10V (20mA)
If the humidity sensor malfunctions, the humidity signal output terminal U1 (I1) will reach 10 V (20 mA) after 60 seconds, while the temperature signal remains normal.
Engineering precautions
To power the sensor, a safe weak current transformer with a separate coil is required. When selecting and protecting transformers, local safety regulations must be followed.
When choosing the size of the transformer, consideration should be given to the power consumption of the air duct temperature sensor.
If you need to wire the sensor correctly, please refer to the sensor technical documentation.
The length of the wire should be within the allowable range.
Cable routing and cable selection
When laying cables, it must be noted that the longer the cable is laid side by side and the smaller the spacing, the greater the electromagnetic interference.
In environments with EMC issues, shielded protective cables must be used.
Twisted pair cables must be used in secondary power supply lines and signal lines.
Installation precautions
position
The sensor should be installed in the middle section of the air duct. If the sensor is shared with a steam humidifier, the shortest distance between them is 3 meters and the longest is no more than 10 meters.
If dew point temperature drift is also involved, the sensor must be installed in the exhaust duct.
Attention
The seal between the shells cannot be removed, otherwise the protection level of IP 65 cannot be guaranteed.
The sensing elements of the sensor head are very sensitive, avoiding excessive vibration or other effects during installation.
Installation Instructions
Installation instructions are printed on the packaging of the sensor
Debugging precautions
Before switching on or off the power supply, check the circuit. If necessary, the temperature measurement range of the sensor should be selected.
Siemens QFM2160 QFM2171 and other series sensors - Technical data
Working voltage: AC 24 V ± 20% or DC 13.5... 35 V; Frequency: 50/60 Hz at AC 24 V; Power consumption: ≤ 1 VA
humidity
Measurement range: 0... 95% r.h
Measurement accuracy at 23 ° C: 0... 95% r.h. ± 5%; 30...70% r.h. ± 3 %
Temperature correlation: ≤ 0.01% r.h./° C
Time constant: approximately 20 seconds in moving air
Output signal: Linear (terminal U1) DC 0... 10 V 0... 100% r.h. max ± 1 mA
Output signal: Linear (terminal I1) simulated load 4... 20 mA 0... 100% r.h
temperature
Temperature range: 0... 50 ° C (R2=factory setting), -35...+35 ° C (R1), -40... 70 ° C (R3)
Measuring element: Pt 1000 class B to DIN EN 60 751
Measurement accuracy: ± 0.6 K (15... 35 ° C); ± 0.8 K(− 35...+70 °C)
The time constant for motion in air is about 20 seconds
Output signal, linear (terminal U2) DC 0... 10 V 0... 50 ° C/-35...+35 ° C/0... 70 ° C max ± 1 mA
Output signal, linear (terminal I2) simulation load 4.20 mA 0... 50/-35...+35/0... 70 ° C
Shell: IP 65 to IEC 529
Safety level: III to EN 60 730
Terminal: 1 × 2.5 mm2 or 2 × 1.5 mm2
Cable conduit: (attached) M 16 x 1.5
Work according to IEC 721-3-3
Climate conditions: Class 4K2
Temperature: -40...+70 ° C
Humidity: 0... 95% r. h. (condensable)
Mechanical condition: Class 3M2
Transport IEC 721-3-2
Climate conditions: Class 2K3
Temperature: -25...+70 ° C
Humidity:<95% r. h
Mechanical condition: Class 2M2
Base polycarbonate, RAL 7001 (silver gray)
Panel polycarbonate, RAL 7035 (silver gray)
Immersion rod polycarbonate, RAL 7001 (silver gray)
Filter cap polycarbonate, RAL 7001 (silver gray)
Install flange PA 66 (black)
Wire connected to sealed tube PA, RAL 7035 (silver gray)
Sensor (complete equipment) silicone free
Product Safety
Home automation electrical control EN 60 730-1
Electromagnetic adaptability
Immunity: EN 61000-6-1
Emission: EN 61000-6-3
Compliant with EMC Directive 89/336/EEC
Compliant with the Australian EMC architecture
Radio communication conflict divergence standard
Wireless Communications Act 1992 AS/NZS 3548
Standard UL 873
Including packaging: 0.18kg
terminal

G1, G2 operating voltage DC 13.5... 35 V
U1 signal output DC 0... 10 V corresponds to a relative humidity range of 0... 100%
U2 signal output 4... 20 mA corresponds to a temperature range of 0... 50 ° C/-40... 70 ° C/-35...+35 ° C
I1 signal output 4... 20 mA corresponds to a relative humidity range of 0... 100%
I2 signal output DC 0... 10 V for temperature range 0... 50 ° C/-40... 70 ° C/-35...+35 ° C
Overall dimensions