SBW □ Integrated Temperature Transmitter with Thermocouple and Resistance
OverviewSWB □ Integrated Temperature Transmitter with Thermocouple/Thermistor (hereinafter referred to as the transmitter) is a type of instrument in the DDZ-S series, which can directly replace the DDZ-III temperature transmitter. The transmitter mainly consists of a temperature sensor (thermocouple or thermistor) and a two-wire temperature transmission module. The display product also includes a current display meter. The transmitter can be installed directly in the junction box of the sensor or near the sensor site (wall mounted). Widely used in industries and scientific research fields such as petroleum, chemical, metallurgical, electromechanical, power, aviation, food processing, medical engineering, etc.
Transmission characteristics:
1. Wide operating temperature range, corrosion resistance, vibration resistance, and low static power consumption, safe and reliable;
2. Adopting a two-wire transmission system, with a large signal output of 4-20mA, strong anti-interference ability, and long transmission distance;
3. Equipped with cold end compensation and nonlinear correction, the output signal is linearly related to the measured temperature;
4. It can directly display the measured temperature on site with a display head, and can be used in conjunction with secondary instruments or directly input into a computer control system.
Main technical indicators
| 1. Input signals: thermocouple, thermistor 2. Output signal: 4-20mA DC output 3. Power supply: 24VDC ± 10%, ripple content<1.0% 4. Basic error limits: ± 0.1% (only for thermoelectric), ± 0.2%, ± 0.5% 5. Temperature drift: When the ambient temperature changes by 10 ℃, the output change is ≤± 0.1% (FS) 6. Load capacity: requires 250 Ω 7. Working environment: Temperature range of 0~70 ℃ or -25~85 ℃, relative humidity ≤ 90% |
![]() |
Model specifications
| Model Marking Method SW □□ - □ - □□□ | ||||||||||
| S | B | W | □ | □ | - | □ | - | □ | □ | □ |
| ① Types of temperature measuring components | ② Structure type | ③ Dividing number | ④ Fixed device code | ⑤ Junction box code | ⑥ Outer protective tube diameter code or measuring end code | |||||
| DDZ-S system arrange instrument outside |
become different deliver one first |
warm linear measure instrument outside |
R-thermocouple Z-thermistor |
None - Single 2- Double support |
B - Platinum rhodium 30- Platinum rhodium 6 R - Platinum Rhodium 13 Platinum S - Platinum Rhodium 10 Platinum K - Nickel chromium nickel silicon N - Nickel chromium silicon nickel silicon E - Nickel chromium copper nickel T - Copper Copper Nickel J - Iron Copper Nickel Cu50 copper thermistor Pt100- Platinum Thermistor |
Refer to the corresponding thermocouple and thermistor model codes | ||||
Temperature measurement range
| Graduation | Temperature measurement range ℃ | ||
| B | 400~1400,600~1600,800~1800 | ||
| S | 0~1300,600~1600,400~1400 | ||
| R | 0~1200,300~1600,600~1600 | ||
| K | 0~800,0~1000,0~1300,200~800,400~1300,500~1300 | ||
| N | |||
| E | 0~400,0~600,0~800,0~1000,200~8000 | ||
| T | 0~200,0~300,200~300 | ||
| J | 0~300,0~400,0~600 | ||
| Cu50 | -50~50,0~100,0~150,-50~100,-50~150 | ||
| PT100 | -50~50,0~100,0~200,0~300,0~500,-200~500 | ||
Note: 1. When placing an order, please indicate the model, division number, tolerance (accuracy) level (if not specified, platinum resistance thermometers provide B-level accuracy, B-division thermocouples provide III level accuracy, and other thermocouples provide II level accuracy), fixing device thread or flange size, protective tube diameter, nominal total length (L=l+150), protective tube material, compression nut (if explosion-proof type is not specified, cable compression nut is provided), and quantity.
2. Please indicate the usage conditions as much as possible when placing an order, such as temperature, measuring medium, and pressure, so that we can recommend a reasonable optimization plan.
3. Can provide fieldbus temperature transmitters through protocol