overview
YN-AT501 point type fiber optic temperature measurement is designed for early prediction of faults and fires caused by insulation aging or poor contact in high-voltage power equipment such as high-voltage switchgear, knife switch switches, cable joints, transformers, etc. Due to the characteristics of electrical insulation, intrinsic safety, and immunity to electromagnetic interference of fiber optic, the probe of the fiber optic sensor can be directly installed on the measured point in a contact manner. By monitoring the temperature abnormalities of switch contacts and cable joints, possible faults can be predicted to prevent electrical fires. The YN-AT501 point type fiber optic temperature measurement device consists of fiber optic sensors, fiber optic thermometers, and fiber optic temperature display devices.
Application scenarios
High voltage switchgear (6KV/10KV/35KV) prone to hot spot monitoring
Monitoring of hotspots in low-voltage switchgear
Monitoring of hotspots such as high-voltage motors
Monitoring of cable joint hotspots
Monitoring of transformer hotspots
Technical Parameter
| name | Technical Parameter |
| Temperature measurement range: | -40℃~200℃ |
| Temperature measurement accuracy: | ±1℃ |
| Probe size: | 18mm(L)×φ3.5mm |
| Probe material: | High temperature resistant ceramics |
| Fiber optic connector: | FC/PC |
| Tail fiber length: | 3~30m |
| Bending radius: | ≥6cm |
| Voltage resistance level: |
220kV (over a length of 1m) |
| Tensile strength: | ≥20N |
| Tail fiber length: |
4.5m, 8m, 10m, 20m, 30m |