Pipeline air leakage detector PAN341
Positive and negative pressure system air duct and equipment leakage evaluation system(PANDA)
PAN300 series
Positive and negative pressure pipeline evaluation system(PANDA can effectively assist contractors, engineering technicians, and R&D personnel in evaluating the leakage rate of ventilation ducts and equipment. PANDA provides a fast, accurate, and automated pipeline system air leakage testing solution, which is widely used for building energy efficiency.
Complies with international standards
BS EN12237:2003
BS EN1507:2006
DW/143 EUROVENT。
Characteristics and advantages
1. Can complete pipeline air leakage testing under positive and negative pressure conditions
-High air leakage rate: 10-200L/S
-Low air leakage rate: 1-13L/S
2. Accuracy: ± 2.5% of the reading
3. PAN321 model includes TA460-P multifunctional ventilation tester and PVM620 micro pressure gauge
-Automatically calculate and display air leakage in real-time
-Simultaneously display the air leakage factor and static pressure value
-Provide Pass/Tail judgment based on the selected airtightness level
-Automatically convert the actual flow leakage rate to the leakage rate under standard conditions (STP)
-Real time monitoring of changes in atmospheric pressure and temperature
-Data can be stored and easily downloaded, and reports can be generated
-Optional 8934 portable printer
TA460-P measurement interface
TECHNICAL INDEX
model:PAN300 series
Pressure measurement(PVM620)
Range: ± 3735 Pa (± 15 in. W.G.)
Resolution: 0.1 Pa (0.001 in. W.G)
Accuracy:Reading of1% ± 1 Pa(± 0.005 in. W.G.)
Pipeline static pressure range: ± 2500 Pa (± 10 in. W.G), when the air flow is zero
Airflow measurement(TA460-P)
Wilson radiation flow probe:High leakage range10-200l/s (36-720 m3/hr, 21-424 cfm)
15mm conical nozzle:
Low leakage range: 1-13 l/s
(3.6-46.9 m3/hr, 2-27.5 cfm)
Resolution: 0.01 l/s (0.01 m3/hr, 0.01 cfm)
Accuracy:Reading of± 2.5% ± 0.01 l/s
(± 0.04 m3/hr, ± 0.02 cfm)
temperature measurement(TA460-P)
K-type thermocouple EN60584 (IEC 584)
Atmospheric pressure test(TA460-P)
Range: 690 to 1241 hPa (517.5 to 930.87)mm Hg, 20.36 to 36.648 in. Hg)
Accuracy:Reading of± 2%
Power requirements
Model numberPAN321 * 220-240V, single-phase, 50/60 Hz, 10A
Model numberPAN311 * * 220-240V, single-phase, 50/60 Hz, 10A
Weight:71Kg(157lbs.)
Size (length)X width x height):1,130mmx660mmx510mm
*Model: Includes instruments
**Model: Instrument not included
TA460-P
Pipeline Classification Table | |||
Air tightness grade |
Static pressure limit (Ps) |
Limit value of air leakage factor (f)max) m3 .s-1 m-2 |
|
positive pressure |
negative pressure |
||
A |
500 |
500 |
0.027 × pt0.65× 10-3 |
B |
1,000 |
750 |
0.009 × pt0.65× 10-3 |
C |
2,000 |
750 |
0.003 × pt0.65× 10-3 |
D |
2,000 |
750 |
0.001 × pt0.65× 10-3 |