Mechanical and environmental parameters
Chassis structure dimensions: |
482.6mm×178.0mm×350.0mm(Wide)×tall×Deep) |
Normal operating temperature: |
-10℃~50℃ |
Extreme working temperature: |
-20℃~60℃ |
Storage and transportation: |
-25℃~70℃ |
Relative humidity: |
5%~95% |
Atmospheric pressure: |
86~106KPa |
Rated electrical parameters
Frequency: |
50Hz/60Hz |
exchangeWorking power supply: |
AC220V,50Hz/60HzAllowable deviation:-20%~+15% |
power waste: |
0.5VA |
The device is subjected to the above-mentioned overload voltage/After the current is applied, the insulation performance does not decrease. |
Specification
Working power supply: |
AC220V,50Hz/60HzAllowable deviation:-20%~+15% |
Working current: |
0.5A |
Host monitoring frequency band: |
300MHz-2000MHz(High frequency)300MHz-3000MHz(Noise) |
Sensitivity: |
5PC |
Gain: |
65dB |
Standing wave ratio: |
1.5 |
Number of host detection channels: |
7High frequency1noise |
Impedance: |
50ohm |
Sensor interface: |
N-type |
Communication interface: |
RS485, Internet port |
Synchronous processing: |
Software synchronization, AC power synchronization |
Collection accuracy: |
12Bit |
High frequency sensor parameters
Monitoring frequency band: |
300MHz-2000MHz |
Sensitivity: |
5PC |
Gain: |
65dB |
Standing wave ratio: |
1.5 |
Impedance: |
50ohm |
Interface: |
N-type |
Installation method: |
Special stainless steel cable tie external installation/flange internal installation |
Noise sensor parameters
Monitoring frequency band: |
300MHz-3000MHz |
Sensitivity: |
10PC |
Gain: |
65dB |
Standing wave ratio: |
1.5 |
Impedance: |
50ohm |
Interface: |
N-type |
Installation method: |
Strong magnetic installation |
High frequency cable parameters
Outer diameter of inner conductor: |
2.83mm |
Total outer diameter: |
10.2mm |
Maximum usage frequency: |
8000MHz |
Attenuation rate: |
Attenuation rate154dB/km |
Shielding layer: |
Double layer silver plated shielding |
electromagnetic compatibility
Electrostatic DischargeImmunity: |
GB/T 17626.4-2 |
IVlevel |
Radio frequency electromagnetic field radiation immunity: |
GB/T 17626.4-3 |
IIILevel (Network)IVGrade) |
Electric fast transientPulse group immunity: |
GB/T 17626.4-4 |
IVlevel |
surge(Impact) Immunity: |
GB/T 17626.4-5 |
IVlevel |
RF field inductionImmunity to Conducted Disturbances: |
GB/T 17626.4-6 |
IIIlevel |
power frequencymagnetic fieldImmunity: |
GB/T 17626.4-8 |
IVlevel |
Pulse magnetic fieldImmunity: |
GB/T 17626.4-9 |
Vlevel |
dampingoscillating magnetic fieldImmunity: |
GB/T 17626.4-10 |
Vlevel |
Vibration waveImmunity: |
GB/T 17626.4-12 |
IILevel (signal port) |
1.3.6. insulation test
The insulation test complies with: |
GB/T14598.3-93 6.0 |
The impulse voltage test complies with: |
GB/T14598.3-93 8.0 |