Shanghai Zhongrong Yidian Co., Ltd
Home>Products>PT secondary circuit voltage drop/load tester
PT secondary circuit voltage drop/load tester
PT secondary circuit voltage drop/load tester
Product details





Measurement range
>Voltage 0.3-400V>current 5A clamp
>Phase 0-360 degrees>frequency 45-55Hz
>Fully automatic range switching.

Main features
1. Adopting a 320 × 240 dot matrix large screen LCD display, the interface display is clear and intuitive;
2. Detailed operation prompts are displayed in Chinese, and the wiring diagram is displayed according to the wiring method for easy operation; The voltage, ratio difference, angle difference, voltage drop, comprehensive error, conductivity, susceptance and other data of PT and Wh terminals are displayed on the same screen, and the readings are very intuitive;
3. The product has computer networking function and is equipped with RS-232C standard serial communication interface, which can realize the upload and download of data and upper computer management software, simplify on-site operations, and achieve computer management automation;
4. Adopting a 16 bit high-precision A/D converter to ensure sufficient resolution, accuracy, and stability for rapid measurement;
5. It can achieve fully automatic measurement and single-phase measurement, store 200 sets of measurement data, and save the data for 10 years after the instrument is powered off;
6. The use of dedicated cable plugs for wiring is convenient, greatly reducing human wiring errors and improving the efficiency of testing personnel;
7. Able to perform fully automatic measurements in three-phase three wire, three-phase four wire, single-phase, and zero position calibration modes;
During the measurement process, the range automatically switches to achieve fully automatic measurement;
9. Equipped with wiring error judgment function and alarm function for exceeding the measurement range;
10. It has instrument fault self checking and alarm functions, as well as undervoltage, overvoltage, and overcurrent protection functions;
11. The instrument is small in size, light in weight, easy to carry, and very suitable for on-site calibration;
12. Battery power supply, external power supply, and PT power supply are optional.

Product Usage
1. Power parameter testing.
2. PT secondary pressure drop test;
3. PT secondary load test;
4. CT secondary load test;
5. Test the secondary load of the current transformer.
1. Technical indicators for secondary pressure drop testing
1) Measurement range: Deviation (f) 0.0001~± 14.00% Resolution: 0.0001
Angle difference (δ) 0.001~± 480 minutes Resolution: 0.001
Initial voltage range (UPT) 57.7V ± 20% 100V ± 20%
2) Allowable error: Ratio difference ± (1% ratio difference reading+1% angle difference reading+1 word missing)%
Angle difference ± (1% angle difference reading+1% angle difference reading+1 word missing)
Digital voltmeter ± (1% reading missing 1 word) V
Frequency ± (1% reading without a single word) Hz
Maximum impulse current: 100mA


2. Technical indicators for PT secondary load testing
1) Measurement range: Conductivity (G) 0.0001~± 50.0ms Resolution: 0.0001
Dianna (b) 0.001~± 50.0ms Resolution: 0.001
Apparent power (S) 0.0001~± 600.0VA (as indirect measurement data)
PT secondary current (I2) 0.001~± 6.00A (indirect measurement data)
2) Allowable error: Conductivity ± (1% conductivity reading+1% electronegativity reading+1 digit) ms
Dianna ± (1% Dianna reading+1% conductivity reading+1 digit) ms
Digital voltmeter (1% reading missing 1 word) V
Frequency (1% reading without a single word) Hz
Current sampling clamp CT 5A (0.2 level)


3. Technical indicators for CT secondary load testing
1) Measurement range: Resistance (R) 0.001~± 99.99 Ω Resolution: 0.001
Reactance (X) 0.001~± 99.99 Ω Resolution: 0.001
Synthetic impedance (Z) 0.0001~± 20.0 Ω
Working current range (I) When In=1A (0.0500-1.200) A
When In=5A (0.250-6.00) A
2) Allowable error: Resistance ± (1% resistance reading+1% reactance reading+last digit 1 word) ms
Reactance ± (1% reactance reading+1% resistance reading+1 digit) ms


4. Usage conditions
1) Working frequency: 50Hz ± 0.5Hz
2) Waveform distortion: ≤ 5 %
3) Temperature:- 10~40� C
4) Relative humidity:< 85%
5) Altitude:< 2500m


5. External dimensions
275 × 245 × 145 (mm) Weight: 5Kg
Configuration Details
1. 5A clamp current transformer (0.2 level) 1 piece
2. Measure 3 wires (four core)
3. One set of management software
4. One cable car (150M-200M)
5. One communication cable
6. One copy of the product user manual
7. One copy of the factory inspection report for the product

Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!

Successful operation!