Product Introduction
Our company'sData Acquisition Gateway(Data Collection Gateway, abbreviated as)DAGGateway is mainly used inModbus RTUProtocol data andModbus TCPConversion between protocol data. Serial port supportModbus RTUMaster and slave functions, supported on Ethernet endModbus TCPFrom the station function.
Serial port operationModbus RTUDuring the main station, users can be actively collectedModbus RTUThe data from the slave station is saved in the data buffer, and the userModbus TCPThe main station equipment can read and write data buffer through Ethernet port to achieveModbus TCPThe main station andModbus RTUThe function of data exchange between slave stations.
Serial port operationModbus RTUFrom the station, the user'sModbus RTUThe main station device can read and write data buffers through the serial port,Modbus TCPThe main station equipment can also read and write data buffers through Ethernet ports to achieveModbus TCPThe main station andModbus RTUThe function of data exchange between main stations.
Users can use the delivery serviceDagctoolSoftware(PCEdit serial port parameters, Ethernet port parameters, working modes, andModbus RTUInstructions, etc., downloaded through Ethernet portDAGWithin the gateway. It can also be accessed through an Ethernet portDAGExisting interface parameters within the gateway andModbus RTUCommand upload toDagctoolSoftware. Users can combine these interface parameters withModbus RTUSave instructions as files for other purposesDAGGateway device usage.
DAGGateway supports standardsModbusThe protocol can be directly integrated with configuration softwarePLCTheDCSIndustrial control touch screen communication.
Features
1ModbusRegister address mapping to achieveModbus TCPQuick response to requests.
2. User definedModbus RTUInstructions.
3. The instruction sending interval, response timeout, and slave response delay can be set.
4. Support2A serial port that can be used simultaneouslyModbus RTUMaster station or slave station.
5. Supports the most5 aModbus TCPMain site accessDAGGateway.
6. Interface parameters andModbus RTUInstructions can be saved as files, reducing user configuration time.
7. DeliveryWINDOWSThe configuration tool software has a user-friendly interface and simple operation.
8. The error diagnosis function can monitor the communication status of the slave station equipment in real time and quickly eliminate faults.
9. RedundancyDC9~36VDual power input, low power consumption.
10. Industrial grade design, capable of long-term stable operation in harsh environments.
Technical Specifications
Number of Ethernet ports: 1a10/100Madaptive
Number of serial ports: 2A(RS-485/422)
power interface: 2a9-36VDCredundancy
Reverse power protection:have
power consumption: 100mA@24V (Max)
Overall dimensions: L123 x W92 x H27 mm
Installation method:Wall mounted installation
Operating Temperature: -20~+75℃
Storage temperature: -50~+125℃
Operating Temperature: 5%~95% (No condensation)
network protocol: ETHERNETTheARPTheIPTheTCPTheICMPTheModbus TCP
TCPNumber of connections:maximum5a
Serial port protocol: Modbus RTU
RTUnumber of instruction:most512article
Serial port baud rate: 300~230400bps
serial port parity bit:No verification, odd verification, even verification
RS-485driving capability: RS-485Maximum interface support32aRS-485Slave station (without relay)
Modbusfunction code: 0x01The0x02The0x03The0x04The0x05The0x06The0x0FThe0x10
Modbusdata buffer
0X zone (coil output)8192One, address(0~8191 =0x0000-0x1FFF
)1X8192Zone (discrete input)One, address(0~8191 =
0x0000-0x1FFF)40963XZone (input register)One, address(
0~4095 =0x0000-0x0FFF4096)4XRegion (Keep Register)
One, address(
0~4095 =5120x0000-0x0FFF)Error diagnosis area
1X zone (error flag zone)512One, address(8192-8703 =0x2000-0x21FF
)
3X area (error code area)
One, address(324096-4607 =0x1000-0x11FF)working modeEach serial port of the DAG gateway has two working modes: master and slaveWhen the serial port works in master station mode, it can only be connected without a relay at mostTaiwan
Modbus1 RTUSlave station equipment; This mode is mainly used forModbus TCPThe main station andModbus RTUData communication between slave stations.When the serial port works in slave mode, it can connect toTaiwanModbus RTUThe main station equipment can achieveModbus TCPThe main station andModbus RTUData communication between main stations; It can also be achievedModbus TCP
The main station andModbus RTU
The main station is simultaneously connected to one channel512Modbus RTUData communication from the station; It can also be achievedModbus RTUData communication between main stations.Modbus RTUcommandDAG gateway supports up toarticleModbus RTUInstructions, users can followModbus RTUThe functions of the slave station equipmentDagctoolSoftware to edit what is neededModbus RTU
Instructions. Command download to
DAG4After the gateway,DAGThe gateway will cyclically send each instruction toModbus RTUFrom station equipment. The instructions include: address code, function code, starting address, number of registers, mapping address, immediate write, response timeout, corresponding serial port and other parameters. 8192 data bufferDAG gateway data buffer is divided intoThe regions are:0Xdistrict 8192 DOStorage area, totalIndividual bit register;1Xdistrict 4096 DIStorage area, totalIndividual bit register;3Xdistrict 4096 AI
Storage area, totalOne word register;
4XdistrictAOStorage area, totalA word register.
DAG