Product Introduction
Single channel, dual channel (isolated). |
summary
Certificate No | GYB081021 |
Explosion proof sign | [Exia] IIC (National Explosion proof Safety Supervision and Inspection Station Certification for Instruments and Meters) |
Authentication parameters | |
terminal | 8-7, 11-10 |
Maximum allowable voltage | Um=250V |
voltage | Uo=10.5V |
electric current | Io=16mA |
power | Po=42mW |
capacitance | Co=2.4μF |
inductance | Lo=80mH |
Single input single output wiring diagram
Dual input dual output wiring diagram
terminal number | Terminal Description | |
Safe Zone (Green) | 1 | OUT1A(S-) |
2 | OUT1B(S+) | |
3 | OUT2A(S-) | |
4 | OUT2B(S+) | |
5 | POW(+) | |
6 | POW(-) | |
Dangerous Zone (Blue) | 7 | IN1A |
8 | IN1B | |
10 | IN2A | |
11 | IN2B |
Application 1: Transistor collector output Application 2: Transistor emitter output
Structural Outline Drawing
EVT1/EVT2: Working indicator light: When the input signal is short circuited, the indicator light is green; When the input signal is disconnected, the indicator light is red. |
35mm guide rail installation, please pay attention to stable and firm positioning during installation. |
Please install it vertically as much as possible to facilitate heat dissipation inside the instrument. |
power supply | |
Rated working voltage range | DC 24V±10% |
power consumption |
Single output: ≤ 0.8W, dual output ≤ 1.2W |
Dangerous side | |
Input Signal Type | Contact switch, proximity switch (frequency ≤ 5KHZ) |
Distribution voltage | ≈ 8V (open circuit) |
Short circuit radio wave | ≈8mA |
Safety side | |
Output signal type | Relay/transistor |
Relay output driving capability | 125VAC/0.6A 30VDC/2A |
Relay response time | <5ms |
Transistor output | When collector output (see application 1 for wiring method): High level VCC (≤ 30V), low level ≤ 2.5V |
When the emitter outputs (see application 2 for wiring method): high level VCC-2.5V, low level ≤ 0.5V | |
Input and output characteristics (when set to in-phase control) | |
On site switch closed or input circuit current>2.1mA, output relay or transistor conducting, channel green indicator light on | |
On site switch open circuit or input circuit current < 1.2mA, output relay or transistor non-conductive, channel red indicator light on | |
Input and output inverse control settings | |
Set by panel dial switch J5 (see accompanying manual for details) | |
Dielectric Strength | |
Local security end and non local security end | 2500V,a.c; 1min |
environmental condition | |
ambient temperature | 0~50℃ |
ambient humidity | 5% to 95% RH (non condensing) |
Standard | |
electromagnetic compatibility | Compliant with GB/T18268 Industrial Equipment Application Requirements |
instrument selection
7 | 8 | 9 | 10 | ||||||||
Switch input detection terminal isolation gate NHR-A35 | - | □ | / | □ | - | □ | / | □ | |||
position | specifications | explanatory note |
| |
|
| | | ↓ □ |
| | | | | | | | | | ↓ □ |
|
| | | | | | | | | | ↓ □ |
|||
7/8 | <Input> | ||||||||||
Input I/Input II (select code from list) | |||||||||||
code | Type | ||||||||||
X | No input (limited to output II) | ||||||||||
36 | Switching quantity | ||||||||||
9/10 | <Output> | ||||||||||
Output I/Output II (select code from list) | |||||||||||
code | type | ||||||||||
X | No output (limited to output II) | ||||||||||
K1 | Relay contact | ||||||||||
K2 | transistor |
Switch input detection terminal isolation gate, dual input signal is switch quantity, dual output is relay contact signal.