Detection object
Remaining current, over line current, temperature
working voltage
AC220V±15%/50HZ
power consumption
≤20W(Excluding external devices)
Communication method
TBUS bus communication
Optional specifications
200.400.600.800.1000
Alarm method
audible and visual alarm
ALARM IN
Built in three sets of programmable external control outputs, with contact capacities of 2A/DC24V or 1A/AC220V
Spare battery
DC12V/4.5Ah lead-acid battery×2
Display mode
TFT graphical Chinese LCD display
Distance
≤1500MM(ZR-RVS×1.5MM2)
communication interface
1 CAN bus. 1 RS232 expandable RS485 or CAN bus
Installation method
Wall Mount
operation temperature
—10℃--+55℃
relative humidity
10% -93% RH (non condensing)
External dimensions
410mm×115mm×540mm(Long)×wide×High)
Adaptive detector
HYEF-RT、HYEF-R、HYEF-T2
•supportNode monitoring within 1000, suitable for monitoring large and medium-sized engineering projects;
7-inch true color LCD display, user-friendly operation, easy and convenient to use;
Two bus polarity free design with short-circuit protection function;
•Built in large capacity data storage, capable of classified storage10000 pieces of alarm, fault and other information;
Equipped with three sets of programmable outputs, it can achieve manual and automatic control output;
The circuit is equipped with isolation function, and the operation does not interfere with each other.
Equipment name
Equipment model
specifications
describe
Electrical fire monitoring equipment
HYFP-B
200 points
Note: The monitoring points are data points, which are the total number of residual current transformers, temperature sensors, and overhead current transformers.
400 points
600 points
800 points
1000 points