GSP Pharmaceutical Warehouse Temperature and Humidity Monitoring System
GSP Pharmaceutical Warehouse Temperature and Humidity Monitoring System
Product details
Product Details

▶ GSP Pharmaceutical Warehouse Environmental Temperature and Humidity Monitoring System


This system is a monitoring and management system for environmental temperature and humidity in the circulation of pharmaceutical products, in accordance with the Good Manufacturing Practice (GSP) regulations. Mainly used for remote monitoring and alarm of temperature and humidity in drug warehouses. The system provides strict monitoring and management of the temperature and humidity of the storage environment, and transmits data to a PC for data storage and analysis, and outputs printed curves. In case of equipment abnormalities, it also notifies relevant personnel in various forms of alarms, making the monitoring of the storage environment unmanned or less manned, providing strong guarantees for the management, use, and safe operation of the storage.


▶ Relevant regulatory requirements


Article 4: The allowable error of temperature and humidity measurement equipment in the system shall meet the following requirements:


(1) The measurement range is between 0 ℃ and 40 ℃, with an allowable temperature error of ± 0.5 ℃;


(2) The measurement range is between -25 ℃ and 0 ℃, with an allowable temperature error of ± 1.0 ℃;


(3) The allowable error for relative humidity is ± 3% RH.


Article 5: The system shall automatically monitor and record the temperature and humidity environment during the storage and transportation of drugs without interruption. The system should update the temperature and humidity data of the measuring points at least every minute, automatically record real-time temperature and humidity data at least every 30 minutes during storage, and automatically record real-time temperature data at least every 5 minutes during transportation. When the monitored temperature and humidity exceed the specified range, the system should record real-time temperature and humidity data at least once every minute.


Article 6: When the monitored temperature and humidity data reaches the set critical value or exceeds the specified range, and the system experiences power interruption, the system should be able to provide sound and light alarms on-site and at designated locations, and at the same time, use SMS communication and other methods to alert no less than 3 designated personnel.


▶ System Topology Diagram


▶ System indicators


▶ Monitoring software interface


▶ Mobile device APP monitoring interface