principle structure
Online installation, mechanical flow switch, used for liquid or gas media. Durable plastic, aluminum or stainless steel casing is optional. The medium can push the plunger spring to the set position, and then apply a magnetic field to the reed switch to output a passive on-off signal and provide instantaneous flow trend indication.

characteristic
The sensor components are fixed with double bolts, making the switch applicable to high-frequency vibration working environments.
application
Gas liquid dual-use type, industrial automation/mechanical equipment/air compression industry/refrigeration and air conditioning
technical specifications
Setting range: | See parameter table for details | Shell: POM engineering plastics | |
accuracy: | ± 2.5% total range | Piston: POM engineering plastics | |
Delay: | Depending on the switch point, the minimum is 0.5L/min | Spring: 316L stainless steel SUS1.4310 | |
Switch setting scale: | The medium is water, the temperature is 20 ℃, and the installation position is calibrated in a horizontal installation state. Changes in medium and temperature may have a slight impact on the switch value | seal up: NBR | |
LED light indication: | Active DC24V provides LED display for switch status | FP57... FP Material: | Magnet: Barium |
Traffic display: | Can display the current instantaneous flow trend on site. | Shell: anodized aluminum | |
Wiring method: | Hessman connector (DIN43650) | Piston: POM engineering plastics | |
Output: | Passive reed switch, capacity 24VDC/230VAC | Spring: 316L stainless steel SUS1.4310 | |
0.5A (3A special customization) | seal up: NBR | ||
Voltage resistance: | 15bar (POM plastic) 50bar (aluminum type) | FP57... FA material: | Magnet: Barium |
50bar (bronze alloy) 100bar (stainless steel) | Shell: 316l stainless steel | ||
Customized 200bar (optional) | Piston: POM engineering plastics | ||
Average pressure loss: | 0.25 bar (at 25 L/min) | Spring: 316L stainless steel SUS1.4310 | |
Medium temperature: | Maximum 90 ℃ | seal up: NBR | |
Protection level: | IP65 | FP57... FK2 Material: | Magnet: Barium |
Shell: Bronze alloy UNI EN 12165 | |||
Piston: POM engineering plastics | |||
Spring: 316L stainless steel SUS1.4310 | |||
seal up: NBR | |||
FP57... FB Material: | Magnet: Barium |
Parameter Table
Model | maximum flow | Variable range | G | L | H | B | X | weight | |||||||||||||
L/min (water) | L/min (water) | mm | mm | mm | mm | mm | kg | ||||||||||||||
FP57-008…A(k)008… | 60 | 0.6(0.1)..8(7) | G1/4 | 93 | 61 | 30 | 12 | 0.22(0.53) | |||||||||||||
FP57-010…A(k)008… | 0.6(0.1)..8(7) | G3/8 | 61 | 30 | 15 | 0.20(0.51) | |||||||||||||||
FP57-015…A(k)008… | 0.6(0.1)..8(7) | G1/2 | 61 | 30 | 15 | 0.18(0.48) | |||||||||||||||
FP57-020…A(k)008… | 0.6(0.1)..8(7) | G3/4 | 105 | 65 | 35 | 15 | 0.23(0.65) | ||||||||||||||
FP57-025…A(k)008… | 0.6(0.1)..8(7) | G1 | 67 | 40 | 15 | 0.32(0.82) | |||||||||||||||
FP57-008…A(k)015… | 1(0.5)…15(13) | G1/4 | 93 | 61 | 30 | 12 | 0.22(0.53) | ||||||||||||||
FP57-010…A(k)015… | 1(0.5)…15(13) | G3/8 | 61 | 30 | 15 | 0.20(0.51) | |||||||||||||||
FP57-015…A(k)015… | 1(0.5)…15(13) | G1/2 | 61 | 30 | 15 | 0.18(0.48) | |||||||||||||||
FP57-020…A(k)015… | 1(0.5)…15(13) | G3/4 | 105 | 65 | 35 | 15 | 0.23(0.65) | ||||||||||||||
FP57-025…A(k)015… | 1(0.5)…15(13) | G1 | 105 | 67 | 40 | 15 | 0.32(0.82) | ||||||||||||||
FP57-015…A(k)028… | 2(0.8)…28(25) | G1/2 | 93 | 61 | 30 | 15 | 0.18(0.48) | ||||||||||||||
FP57-020…A(k)028… | 80 | 2(0.8)…28(25) | G3/4 | 105 | 65 | 35 | 15 | 0.23(0.65) | |||||||||||||
FP57-025…A(k)028… | 2(0.8)…28(25) | G1 | 67 | 40 | 15 | 0.32(0.82) | |||||||||||||||
FP57-020…A(k)070… | 120 | 27(21)…70(66) | G3/4 | 65 | 35 | 15 | 0.23(0.65) | ||||||||||||||
FP57-025…A(k)070… | 27(21)…70(66) | G1 | 67 | 40 | 15 | 0.32(0.82) | |||||||||||||||
FP57-032…A(k)… | 150 | 0.6(0.1)..70(66) | G1 1/4 | 150 | 67 | 50 | 15 | 0.52(1.02) |
Note: 1. (*) Parameters in parentheses are reset points, while parameters outside parentheses are action points. If the lower limit alarm (monitoring flow rate is too low), refer to the reset point parameters. Upper limit alarm (monitoring excessive traffic)
Reference action point parameters.
The above parameters were obtained by installing the switch in a horizontal pipeline and testing it with 20 ℃ water as the medium.
dimension





Model Selection Table
FP57- | Double bolt visual plunger flow switch | ||||||||
Applicable pipe diameter | |||||||||
Threaded interface G1/4 nominal diameter DN8 | Threaded interface G3/4 nominal diameter DN20 | ||||||||
Threaded interface G3/8 nominal diameter DN10 | Threaded interface G1 nominal diameter DN25 | ||||||||
Threaded interface G1/2 nominal diameter DN15 | Threaded interface G1 1/4 nominal diameter DN32 | ||||||||
Connection method | |||||||||
Internal thread (female joint) | |||||||||
External thread (male joint) | |||||||||
Flexible hose quick connector (please note the inner diameter of the hose when ordering) | |||||||||
signal type | |||||||||
24V±20%DC,0.5A,26W; Active contact signal; Normally open signal, adjustable range | |||||||||
24V±20%DC,0.5A,26W; Passive contact signal; Normally open signal, adjustable range (without LED indicator light) | |||||||||
24V±20%DC,0.5A,26W; Passive contact signal; Normally closed signal single point setting (without LED indicator light) | |||||||||
24V±20%DC,0.5A,26W; Active power supply normally open+normally closed output, adjustable within the range (Hirschman sealing treatment, flying wire lead out method, cable length needs to be noted) | |||||||||
230V±15%AC,1A,48W; Passive contact signal normally open signal, adjustable within range (without LED indicator light) | |||||||||
230V±15%AC,1A,48W; Passive contact signal normally closed signal single point setting (without LED indicator light) | |||||||||
380V±15%AC ; Passive contact signal normally open signal single point setting (without LED indicator light) | |||||||||
380V±15%AC; Passive contact signal normally closed signal single point setting (without LED indicator light) | |||||||||
AC/DC universal type; Passive contact signal normally open signal, adjustable within range (without LED indicator light) | |||||||||
AC/DC universal type; Passive contact signal normally closed signal single point setting (without LED indicator light) | |||||||||
No output unit, only used for instantaneous flow trend indication | |||||||||
Material description of the liquid receiving body | |||||||||
POM reinforced plastic liquid body | |||||||||
Anodized alumina liquid body | |||||||||
Bronze alloy structure liquid body | |||||||||
Stainless steel 1.4301 (304) liquid body | |||||||||
Stainless steel 1.4435 (316L) liquid body | |||||||||
Alarm setting interval | |||||||||
Normal traffic is less than or equal to 5L (specific customer backup option) | |||||||||
Setting range: 0.6... 8L/min (offline alarm 0.1... 7L/min) | |||||||||
Setting range: 1... 15L/min | |||||||||
Setting range: 2... 28L/min | |||||||||
Setting range: 27... 70L/min | |||||||||
Electrical connection method | |||||||||
Husman terminal connector (DIN43650) | |||||||||
(Special alternative) VARIO | |||||||||
Top view installation of scale indicator surface (without this option, the panel defaults to the front side) | |||||||||
Output two switch quantity alarms |
The above selection table does not include selection codes. If you need selection codes, please contact us or fill in your information |
Top view schematic diagram of scale window