Shandong Longyi Instrument Technology Co., Ltd
Home>Products>Dual circuit display intelligent instrument
Dual circuit display intelligent instrument
XMS161 Dual Loop Display Intelligent Instrument
Product details


XMS161双回路显示智能仪表

XMS161 dual circuit display intelligent instrument.

1. Intelligent rapid inspection instrument is a fast instrument for domestic inspection, with a sampling time of 50mS for each inspection channel

2. Using a 24 bit A/D converter, the measurement accuracy is 0.2% Fs ± 1 word

3. Using differential input to effectively suppress interference between input signals

4. This instrument has a 16 channel patrol detection function, and the inspection channels within the 16 channels can be freely set by software

5. Each channel can support 17 types of input signals, and the input signal type can be freely selected through software.

6. During automatic inspection, the display time for each inspection channel can be set, automatic inspection can be paused, and the inspection channel can be manually switched

7. One of the 16 channels can be selected as an "important channel", which is frequently displayed and equipped with independent upper and lower limit alarm relays. It can be used for control or self-protection

8. Powerful network communication capabilities, providing testing software and technical support (MODBUS RTU protocol, RS485)

9. Printing interface with real-time clock, optional for timed and manual printing; 42 printing units covering chemical, ceramic, metallurgical, and petrochemical industries

10. Measurement units for temperature, humidity, flow rate, pressure, liquid level, etc. in industries such as heat treatment

11. The upper and lower limit alarm values of each channel are independently set, with flashing alarm and alarm release functions

Technical Parameter

1. Power supply voltage: AC 160V~265V

2. Accuracy: 0.2% FS ± 1 word

3. Sampling time for each inspection channel: 50mS

4. Display range: -1999 to 9999 words

5. Display mode: 0.56 "LED display

6. Disconnected display: When the input signal is a thermocouple or thermal resistor, the input circuit is disconnected and displays "EEEE"

7. Parameter setting: Set through panel buttons or communication port on the upper computer. After setting the parameters, the password is locked

8. Communication output: RS485, baud rate 1200-9600pcs, optoelectronic isolation (MODBUS_STU protocol)

9. Printing interface: Serial RS232 printer, baud rate 9600pbs

10. Usage environment: ambient temperature 0-50 ℃, relative humidity<90% RH, avoid strong corrosive gases

Dimensions: 160 × 80 × 148mm (horizontal), disc mounted card in type.Intelligent thermometer manufacturer.