The XBC-GISO diesel engine fire pump equipment consists of a diesel engine, pump, fuel tank, steel base, and control system. It is a high-tech product that integrates industrial automation control technology, information processing technology, and mechanical operation technology. The unit can achieve functions such as automatic start stop, automatic speed regulation, automatic charging, parameter detection, automatic alarm, automatic inspection, remote control, etc. With the improvement of national fire safety regulations and the increasing awareness of fire safety among people, the application of diesel engine fire pump sets is becoming more and more common. Our professional technical personnel have developed a new generation of diesel engine fire pump sets in accordance with relevant standards, industry and local regulations. The pump set covers different work requirements from small flow to large flow, low head to high head.
XBC-GISO diesel engine fire pump product features
1. Automatic start: After receiving a fire alarm/pipeline pressure/power outage/or other start signal, the diesel pump unit can automatically start and operate at full load within 15 seconds;
2. Automatic charging: The battery can be charged automatically by the mains power or diesel engine charging motor to ensure the smooth start-up of the unit;
3. Automatic alarm: Automatic alarm protection for diesel engine low oil pressure, high water temperature and other faults, and alarm and stop when overspeed occurs again;
4. Automatic preheating: put the diesel engine in a hot standby state to ensure emergency operation;
5. Direct connection type: Diesel engine pump units below 360kw adopt domestic diesel engine and water pump direct connection technology through elastic couplings, reducing fault points and greatly shortening the starting time of the unit, increasing the reliability and emergency performance of the unit;
Working conditions and performance parameter range
Pump operating range
·Flow rate: 100-430L/S
·Lift: 60-185m
·Transmission medium: ordinary clean water and fire foam liquid
Diesel engine operating range
·Environmental temperature: -25~55 ° C
·Relative humidity:<85%
·Longitudinal inclination during work:<10 °
·A place without conductive dust, corrosive gases that damage metal insulation, and explosion hazards.
·Relative humidity:<85%. If the ambient temperature is above 20 ° C or the relative humidity exceeds 30% or the altitude exceeds 1000 meters, the diesel engine power should be corrected. The correction factor should be selected based on the data table provided by the diesel engine manufacturer.
Scope of work for control cabinet
·Power supply voltage fluctuation: ≤± 10%
·Surrounding ambient temperature: -10~+40 ° C (not frozen)
·Relative air temperature: 20%~90% (no condensation)
Product Usage
·Diesel engine fire pump sets are mainly used for fire water supply in mines, oil depots, stations, airports, docks, buildings, schools, factories, and other places. They can also be used for temporary municipal drainage, temporary irrigation of farmland, and other occasions.