1Product Features
lDC7-30VWide voltage power supply;
lInput optocoupler isolation, relay output contact isolation;
lCommunication interface supportRJ45EtherNet;
lSupported StandardsmodbusProtocol, while also supportingRTU/TCPformat;
lEquipped with flashing and breaking functions, it can include parameters in the command and operate the relay to automatically turn off after a period of time;
lEquipped with strobe function, it can control the periodic switching of relays;
IIPRODUCT FUNCTION
l2Road optical coupling input(DC3.3-24V);
l2Road relay output;
l2road12Bit resolution analog voltage input;
lSupporting baud rate:2400,4800,9600,19200,38400(Can be modified through software, default)9600);
lDevice defaultIPdo192.168.1.232, port number10000.
Intelligent self-control version features:
ltiming control----Custom time control settings for year, month, day, hour, minute, and second, which can be looped;
lOutput interlock----The interlocking relationship between custom output channels and output channels;
lSwitching linkage----Manual switch or switch triggered device is linked with control output;
lAnalog automatic control----Customize the upper and lower limit thresholds for analog signals, and automatically control them upon triggering;
lscene control-----Customize complete logic control triggering conditions;
l70Group rule setting----up to70Set group rule conditions to meet various logical requirements.
3、 Version Description
① TheNormal version:
lThe default input and output of the device are independent of each other and have no relationship.
② Intelligent self-control version:
ltiming control----Custom time control settings for year, month, day, hour, minute, and second, which can be looped;
lOutput interlock----The interlocking relationship between custom output channels and output channels;
lSwitching linkage----Manual switch or switch triggered device is linked with control output;
lAnalog automatic control----Customize the upper and lower limit thresholds for analog signals, and automatically control them upon triggering;
lscene control-----Customize complete logic control triggering conditions;
l70Group rule setting----up to70Set group rule conditions to meet various logical requirements.
4Parameters
5Interface Description
6、 Communication instructions
1、defaultIP
2、reset key
7、 Quick instructions for use
1Equipment power supply;
2Connect the network cable;
3Configure parameters through software on the computer side;
Open Ethernet configuration software to connect device configuration parameters
4Open the LAN platform software and add it for use.
8、 Input/outputwire connection
1、Schematic diagram of active switch wiring
2、Schematic diagram of passive switch wiring
3、Relay wiring instructions
4、Analog wiring diagram
Collected by devicesThe relationship between AI data and actual input values:
actualprice=returnprice*0.001
9Equipment parameter configuration
1Network configuration instructions
oneNetwork interfaceVersion device passedEthernet configuration software for parameter and working mode configuration, detailed configuration methods, read【Ethernet configuration softwareinstructions】Documents are sufficient;
Ethernet configuration software download address:
http://www.juyingele.com.cn/software/jynet/Ethernet configuration software.rar
2、Working mode
① Regular version:
The default input and output of the device are independent of each other and have no relationship.
② Intelligent self-control version:
Switching quantity(DI)Input and analog quantities(AI)Input and relay output(DO)The corresponding relationship needs to be usedDLCConfigure software or directly configure on cloud platform software.
DLCConfigure software download address:
http://www.juyingele.com.cn/zlxz/danziliao/1101.html
11、 Development documentation description
1、communicationProtocol Specification
This product supports standardsmodbusInstructions, for detailed instruction generation and parsing methods, please refer to the register table in this article for reference《MODBUSThe Chinese version of the agreement is sufficient.
ModbusagreementDownload link for the manual:
http://www.juyingele.com.cn/software/software/Modbus%20POLLSoftware and User Manual.rar
2、ModbusRegister Description
Coil register address table:
3、Instruction generation instructions
Instructions can be obtained throughJu Ying SoarsDAMDebugging software ",checkDebug information to obtain.
Instruction generation instructions: For instructions not listed in the table below, users can generate them themselves according to the instructions providedmodbusProtocol generation, for the reading and writing of relay coils, is actually aboutmodbusThe reading and writing of the coil register in the register. The address of the relay register has been explained in the previous text, and users only need to generate read and write instructions for the register operation. For example, reading or writing relays1The state is actually related to the relay1Corresponding coil register00001Read and write operations.
4、instruction list
5、Instruction Explanation
5.1、Relay
control1-channel relay (taking the first channel as an example, refer to this example for other channels)Any byte change,The CRC checksum will change accordingly.
Send code:FE 05 00 00 FF 00 98 35
Relay card return information:
Return code:FE 05 00 00 FF 00 98 35
5.2、relay status
query2Road relay
Send code:FE 01 00 00 00 02 A9 C4
Relay card return information:
Return code:FE 01 01 00 61 9C
5.3、Optocoupler input
Query optocoupler
Send code:FE 02 00 00 00 02 ED C4
Optocoupler return information:
Return code:FE 02 01 01 50 5C
5.4、Analog quantity query
The relationship between the obtained analog data and the actual input value is: actual value=return value*0.001
Query analog quantityAD character
Send code:FE 04 00 00 00 02 64 C4
Simulated return information:
Return code:FE 04 02 00 00 AD 24
5.5、Flash open/close command
Analysis of Flash Open and Flash Close Instructions
Flash development code:FE 10 00 0300 02 04 00 04 00 0A41 6B
Flashing sending code:FE 10 00 03 00 02 04 00 02 00 14 21 62
Return code:FE 10 00 03 00 02 A5 C7
5.6、Fully open and fully close command
Analysis of fully open and fully closed commands
Full development code submission:FE 0F 00 00 00 0201 FFD1 D3
Completely disconnect sending code:FE 0F 00 00 00 0201 0091 93
Full open return code:FE 0F 00 00 00 02 C0 05
Total disconnect return code:FE 0F 00 00 00 02 C0 05
tentwoTechnical support contact information
contact number:010-82899827/1
contactQQ:3323725294 2984784459