Product Features: |
|
• The differential pressure range can be set by oneself |
|
• Display screen: with or without LCD digital display screen |
|
Manual differential pressure zero calibration through buttons |
|
• Shell: ABS industrial plastic - IP 65 |
|
• Set up through software or toggle switches |
|
The rotation method is fixed to the installation backboard |
|
technical specifications: |
|||
|
range |
CP 112 |
-1000~+1000 Pa (minimum can be set to 0~+100 Pa) |
|
|
|
CP 113 |
-1000~+1000 mmH2O (minimum can be set to 0~+100 mmH2O) |
|
|
|
CP 114 |
-500~+500 mbar (minimum can be set to 0~+100 mbar) |
|
|
|
CP 115 |
-2000~+2000 mbar (minimum can be set to 0~+500 mbar) |
|
|
|
|||
|
accuracy |
± 1% measurement value |
||
|
|
|||
|
Pressure Unit |
CP112 / CP113 |
Pa, mmH2O, mbar, inH2O, mmHg, daPa, KPa, hPa, mbar |
|
|
|
CP114 / CP115 |
mmH2O, mbar, inH2O, mmHg, KPa, daPa, hPa, PSI |
|
|
|
|||
|
Allow overvoltage |
CP 112 |
21,000 Pa |
|
|
|
CP 113 |
69,000 Pa |
|
|
|
CP 114 |
1,400 mbar |
|
|
|
CP 115 |
4,100 mbar |
|
|
|
|||
|
output signal |
1 set of 4~20 mA or 0~10 V (3/4 wire type) |
||
|
|
1 set of 4-20 mA (2-wire type) |
||
|
|
|||
|
power supply |
24 VAC/VDC (3/4 wire type) |
||
|
|
16~30 VDC (2-wire type) |
||