Application of Zinc Oxide Surge Arrester Online Monitoring System
Product Usage
It is an instrument used to test the electrical performance of zinc oxide lightning arresters. This instrument is suitable for live or power-off detection of zinc oxide lightning arresters of various voltage levels, so as to timely detect dangerous defects such as insulation moisture and valve plate aging inside the equipment.
The instrument is easy to operate and use, and the entire measurement process is controlled by an industrial computer. It can measure the full current, resistive current and its harmonics, power frequency reference voltage and its harmonics, active power and phase difference of zinc oxide lightning arrester. The large screen can display the real waveforms of voltage and current. The instrument utilizes digital waveform analysis technology and employs software anti-interference methods such as harmonic analysis and digital filtering to ensure accurate and stable measurement results. It can accurately analyze the fundamental wave and3~7The content of subharmonics can overcome the interference between phases and accurately measure the resistive current of edge phase lightning arresters.
Application of Zinc Oxide Surge Arrester Online Monitoring System
Product Features
800×480Color LCD touch screen,High speed thermal printer; Graphic and textual display, intuitive interface, easy for on-site personnel to operate and use.
wireless transmissionPTSignal exceeds400riceOn demand configuration can achieve2000rice.
Suitable for use in places with live lightning arresters, power outages, or laboratories.
Truly achieving simultaneous testing of three-phase current and three-phase voltage to improve work efficiency; The instrument only has weak electricity inside, and the voltage does not exceed12VThe current and voltage sensors are isolated, safe and reliable.
Supports two voltage reference signal sampling methods: wired synchronization and wireless synchronization; It also supports voltage free mode, where the voltage reference can be found through software calculation.
Equipped with high-energy lithium-ion batteries, especially suitable for situations without power supply.
Equipped with an embedded industrial grade operating system, supporting direct shutdown mode; Equipped with oneUSBInterface, supportsUExport data from disk; Can be added externallyUSBMouse and keyboard usage, easy to operate.
internal configuration4GBCapacity ofSDThe card can store massive amounts of experimental data and has functions such as data management and storage.
Equipped with upper level management software, it has functions such as historical data management, data analysis, and report printing.
High speed sampling frequency, advanced digital signal processing technology, strong anti-interference performance, and measurement result accuracy *.
Adopting dust-proof, waterproof, and anti-corrosion engineering plastic sealing box, it has a small volume, light weight, and is easy to carry.
IIILyyb- 2000technical indicators
power supply220VThe50HzOr powered by internal batteries
Measurement range:
leakage current0-10mA(Scalable);
voltage30-100V(Scalable).
Measurement accuracy:
Current: Full current>100MATime: ±5%Reading ±1One word;
Voltage: reference voltage signal>30VTime: ±5%Reading ±1One word.
Measurement parameters:
Leakage current full current waveform, fundamental effective value, and peak value.
Effective value of the fundamental wave of the resistive component of leakage current and3、5、7The second most significant value.
Peak value of resistive component of leakage current: positive peak valueIr+Negative peak valueIr-.
Fundamental wave of capacitive current, phase difference between full voltage and full current.
Effective voltage value.
Power consumption of lightning arrester.
Voltage reference signal sampling method:
Wired synchronization:40rice(Scalable)
Wireless synchronization:>400rice(Scalable)