product overview
Used for monitoring the density of gas in sealed containers, it can be widely applied in medium voltage switchgear and ring main unit. We can provide various solutions such as supporting new substations and renovating existing substations. On the basis of the original density relay, this product has added calibration and air supply interfaces. It has achieved online verification of the current working density relay without disassembling it, and can also replenish the air chamber. Meet the requirements outlined in the State Grid testing outline.
SF6 gas insulated ring main unit
SF6 gas insulated switchgear
product overview
Used for monitoring the density of gas in sealed containers, it can be widely applied in medium voltage switchgear and ring main unit. We can provide various solutions such as supporting new substations and renovating existing substations. On the basis of the original density relay, this product has added calibration and air supply interfaces. It has achieved online verification of the current working density relay without disassembling it, and can also replenish the air chamber. Meet the requirements outlined in the State Grid testing outline.
Technical Parameter
Shell diameter: Φ64mm
Shell material: stainless steel
Measurement range: 0~2 bar (abs.) or -1~6 bar
Measurement accuracy: Level 1.5 (at 20 ℃); Level 2.5 (at -30 ℃~+60 ℃) (gaseous)
Working temperature: -30 ℃~+60 ℃, relative humidity ≤ 95% RH
Protection level: IP65
Leakage rate: ≤ 1×10-9Pa·m3/S (helium leak detection)
Contact type: Magnetic assisted electric contact switch (maximum 3 groups, normally open or normally closed)
Body interface: M20 × 1.5 (customizable)
Verification air supply interface: M16X1.5 (requires dedicated inflation and verification adapter, adapter size can be customized)
Installation method: radial or axial
Insulation performance: Insulation resistance:> 100M (DC 500V)
Power frequency withstand voltage: 2000V, 50/60 Hz 1 min
Contact electrical parameters: Power: 30VA
Maximum operating voltage: 380V
Maximum passing current: 1A
Weight: 0.5kg
18. Pressure sensing element: Burton tube