The combination of remote density relay and dew point sensor enables on-site collection and processing, while reporting density, pressure, temperature, and micro water content information.
Used for monitoring sealed containersSF6The density, pressure, temperature, and micro water content of the gas can be displayed on site, and an alarm can be triggered when the density value reaches the set value, with real-time remote transmissionSF6Gas densityPressure, temperature, micro waterData, realize online remote monitoring function. Suitable for monitoring high-voltage systems, it can provide various solutions such as supporting new substations and intelligent transformation of existing substations.
SF6Insulated composite electrical appliances(GIS)
SF6Insulated Circuit Breaker
SF6Insulated pole switch
SF6insulating transformer
SF6Insulation Transformer
SF6Insulated busbar system
1. Equipped with temperature compensation device for higher measurement accuracy
2. Suitable for different installation needs indoors and outdoors
3. selectAISI 304Stainless steel made sealed case
4. selectAISI 316Stainless steel made pneumatic connection components
5. The on-site display values and output signals are not affected by external factors such as altitude
6. Integrated design of combined collection device, effectively ensuring airtightness
7. The combined collection device only occupies one ventilation port, reducing the risk of air leakage
8. The combination of remote density relay and dew point sensor enables on-site collection and processing, while reporting density, pressure, temperature, and micro water content information
9. Acquisition deviceuseRS485communicationway, convenient for on-site networking and debugging
10. All monitoring points within the interval can be conveniently accessed through dedicated channelsRS485Hub Implementation and IntelligenceIEDOr backend serverInterconnection reduces the number of communication ports and saves resources
1Shell diameter:100mm
2Measurement range: Density:-0.1 ~ 0.9MPa(Customizable)
the dew point:-50°CDP~ 30°CDP(Working status)
3Measurement accuracy: (depends on the measurement range, andSF6For gaseous state)
a)20°C: 1.0level,perhaps1.5level
b)-40°C~+60°C: 2.5level
the dew point:±3°CDP
4Protection level:IP65
5Operating temperature:-40°C~ +60°C,relative humidity≤95%RH
6Leakage rate:≤1×10-9Pa·m3/s (Helium leak detection)
7Interface size:M20×1.5(Can)Customized)
8Installation method: radial or axial
9Electrical connection: plug-in connectionM20×1.5Sealing head
Cable size: recommended1.5mm2,maximum2.5mm2
10Insulation performance: Insulation resistance:>100 MW(DC 500V)
Power frequency withstand voltage:2kV,50/60 Hz 1min
11Contact type: magnetic assisted electric contact switch
80%Silver20%Nickel,10µmgold-plating
12Impact level:50g (Oil filled type), 30g(Non oil filled type)
13Electrical parameters of contacts:30W/50VA, 1A.(Maximum)
220VDC/380V 50/60Hz(maximum)
14Table glass: multi-layer safety glass
15Weight:5.5kg
16Pressure sensing component: imported Burton tube
Main electrical performance indicators and specifications for remote transmission
lWorking voltage:DC 24V
lpower waste: <>
lCommunication method:RS485
lCommunication protocol:ModBusRTU
lTransmission speed:9600bps
lanti-electromagnetic interferenceIEC61000-4-2:4level(15kV)
IEC61000-4-3:3level(10V/m)
IEC61000-4-4:4level(4kV)
IEC61000-4-5:3Grade(+/-2kV)
IEC61000-4-6:3Grade(10V)
IEC61000-4-8:5Grade(100A/m)
power-frequency withstand voltage2.5kV 50/60 Hz 1min
Refillable oil
Measurement medium:SF6、Air、N2、SF6+N2Waiting for gas