VIP member
YN194E-3S4T Short Shell Multifunctional Power Meter
YN194E-3S4T Short Shell Multifunctional Power Meter
Product details
Measurement: three-phase phase voltage, line voltage, current, total active power, total reactive power, total power factor, total apparent power, active energy, reactive energy
● Display: LED digital tube display or STN blue screen, wide viewing angle, high-quality, high-definition LCD screen display, high visibility.
Communication: 1 RS485 communication channel, MODBUS-RTU protocol.
Output: 2-channel electric energy pulse output (pulse constant 5000imp/kwh)
Expansion: It can directly input signals from voltage and current transformers, and the input parameter ratio can be programmed on site.
summary:
performance | parameter | ||
transport enter measure measure apparent show |
voltage | network | Three phase three wire, three phase four wire |
RATING | AC380V/220V (please specify other specifications when ordering) | ||
overload | Overload: 1.2 times instantaneous: 10 times/10 seconds | ||
power consumption | < 1VA (per phase) | ||
impedance | >500KΩ | ||
accuracy | RMS measurement, accuracy level 0.5 | ||
electric current | RATING | AC5A (other specifications, please specify when ordering) | |
overload | Overload: 1.2 times instantaneous: 10 times/10 seconds | ||
power consumption | < 0.4VA (per phase) | ||
impedance | >2MΩ | ||
accuracy | RMS measurement, accuracy level 0.5 | ||
frequency | resolution | 0.1HZ | |
measuring range | 45~65HZ | ||
power | accuracy | Active power accuracy level 1.0, reactive power accuracy level 1.5 | |
electric energy | accuracy | Four quadrant measurement, active power accuracy level 1.0, reactive power accuracy level 1.5 | |
power supply | scope of work | AC/DC85~270V | |
power consumption | ≤5VA | ||
output | Digital Interface | RS485, MODBUS-RTU protocol | |
pulse output | 2-channel power pulse output, pulse constant: 5000imp/kwh | ||
environment | work environment | -10~55℃ | |
Environment | -20~75℃ | ||
secure | pressure resistance | Input/power>2kV, input/output>2kV, power/output>1kV | |
isolation | Input, output, and power supply to the chassis>50M Ω | ||
Electric energy measurement range | The measurement range for active and reactive electricity is from 0 to Mwh. If the value exceeds this range, the electricity will be counted from 0 |
Additional features:
Ordering method:
modelYN194E-9S4T (Multi functional Power Meter)
Power network: three-phase four wire
Online inquiry