1、 Overview of temperature and humidity transmitter: The ARSWS200 temperature and humidity transmitter adopts a wall mounted waterproof shell, which is commonly used in outdoor and harsh on-site environments. Multiple types of probes are available for different sites, widely used in communication rooms, warehouse buildings, and places that require temperature monitoring such as automation. Adopting standard industrial interface 4-20mA/0-10V/0-5V analog signal output, it can be connected to on-site digital display meters, PLCs, frequency converters, industrial control hosts and other equipment. Safe and reliable, aesthetically pleasing, and easy to install. 2、 Functional features: The ARSWS200 temperature and humidity transmitter adopts a measurement unit imported from Switzerland, which measures accurately. Using dedicated analog circuits with a wide range of applications. Power supply with a wide voltage range of 10-30V, complete specifications, and easy installation. Can be applied to both four wire and three wire connection methods simultaneously. 3、 Technical specifications of temperature and humidity transmitter:
DC power supply (default)
|
10~30V DC
|
Maximum power consumption
|
current output
|
1.2W
|
Voltage Output
|
1.2W
|
accuracy
(Default)
|
humidity
|
±3%RH(5%RH~95%RH,25℃)
|
temperature
|
±0.5℃(25℃)
|
Operating temperature of transmitter circuit
|
-40℃~+60℃,0%RH~80%RH
|
Probe operating temperature
|
-40℃~+120℃, default-40℃~+80℃
|
Probe working humidity
|
0%RH-100%RH
|
Long term stability
|
humidity
|
≤1%RH/y
|
temperature
|
≤0.1℃/y
|
response time
|
humidity
|
≤8s(1m/swind speed)
|
temperature
|
≤25s(1m/swind speed)
|
output signal
|
current output
|
4~20mA
|
Voltage Output
|
0~5V/0~10V
|
Load capacity
|
Voltage Output
|
Output resistance ≤250Ω
|
current output
|
≤600Ω
|
4、 Selection of temperature and humidity transmitters:
|