overview
Suitable for small and medium-sized enterprises, commercial users and other public billing electricity data measurement and metering places;
main features
DTZY1778-ZThe three-phase cost controlled energy meter adopts high-precision MCU and high-precision circuit design, which has the characteristics of stable performance, rich functions, and strong anti-interference ability. Its functions include time-sharing rate, switch control, etc. The functional configuration is flexible, and it has multiple optional functions to meet the needs of various places;
major function
Ø It can measure voltage, current, and power, measure positive and negative active energy, four quadrant reactive energy, and demand data, and has power direction recognition and indication functions;
Ø The cumulative storage of electricity data and demand data can last up to 12 months, supporting up to 3 settlements within a month;
Ø Support any combination of active and reactive power, and can separately measure phase separated positive and negative active energy as well as four quadrant reactive energy;
Ø It has the function of time division multiple rate electricity metering, which measures positive and negative active power and four quadrant reactive power in a time-sharing manner, as well as the corresponding maximum demand;
Ø Maximum support for 4 rates, switching between two rate periods; The time slot rate parameters can be modified through parameter setting software;
Ø It can record and store 6 types of load records, multiple frozen records, and comprehensive event records, and has anti electricity theft and lid opening detection function;
Ø Equipped with built-in or external relay control, the relay is configured according to current specifications;
Ø It has rich self checking, error correction, alarm and security prevention functions;
Ø Equipped with backlit LCD display, supporting rich status indicators and Chinese auxiliary information prompts;
Ø Supports RS-485 and infrared communication, with optional carrier communication methods, both supporting DL/T645-2007 and Q/GDW11778-2017 protocols;
Ø After a power outage, the display meter reading can be awakened through buttons and handheld devices;
Ø The infrared baud rate is 1200bps, and the default baud rate for 485 is 2400bps. The baud rate can be modified to 1200-9600 through parameter setting software;
performance parameter
project |
TECHNICAL INDEX |
Main technical standards |
GB/T17215.321-2008;GB/T17215.322-2008; GB/T17215.323-2008; DL/T614-2007 |
reference voltage |
AC 3×220/380V,3×57.7/100V,3×100V; Resolution: 0.1V |
Working voltage range |
70%Un~120%Un |
Common current specifications |
Mutual inductance type 1.5 (6) A; Direct equation 5 (60) A; Resolution: 0.001A; (Specifications can be customized according to requirements) |
power |
Resolution: 0.0001KW/Kvar |
active electrical energy |
Accuracy level: active 0.5S level, 1 level, 2 level, reactive 2 level; Resolution: 0.01KWh |
Working power supply |
No need for external power supply (direct power supply) |
Load switch |
Built in or external |
operation temperature |
-25℃~+60 ℃, maximum operating temperature:- 40℃~+70℃ |
Frequency range |
(50±2.5)Hz |
Clock Error |
23℃,≤ 0.5s/d;- 25℃~+60℃,≤ 1.0s/d |
Communication protocol |
DL/T645-2007, Q/GDW11778-2017 |
External dimensions |
Length x Width x Thickness: 290mm x 170mm x 85mm |
Product wiring diagram