Passive contact switch quantity (normally open or normally closed)
Level input control signal (high or low), high level ≥4V
output signal
Alarm output: Output a pair of passive normally open contact switches (closed upon alarm). The contact action is synchronized with the alarm sound. CONTACT CAPACITY5A/24VDC、5A/220VAC
Speaker output: Output a pair of speaker drivers, can be externally connected8Ω/1WLoudspeaker produces sound
TECHNICAL INDEX
Line input resistance: ≥50Ω
Recording and playback length:6second/road
Power supply: ACAC220V, DCDC24V.
workConsumption: ≤ when an alarm is triggered5WWhen there is no alarm, ≤0.5W
Usage environment
Relative temperature -10~50℃
relative humidity≤85%RH,No condensation, no corrosive gas
atmospheric pressure 86~106kPa
typename
take the place ofa sign or object indicating number
speakbright
SWP-
□
□□□
-□
-□
-□
-□
-□
characteristic
X
Parameter display: Eight digit high brightnessLEDChannel display
Control function
803
Flash alarm device
Communication method
□
0: No communication;2:RS-232;8:RS-485
Instruction method
D
N
R
Eight segment digital tube indication
planeLEDInstruction (no communication)
planeLEDIndication (with recording and playback function)
Input signal
A
B
C
D
Contact type closed-circuit alarm
Contact type open circuit alarm
standardTTLlevel
Special specifications
Feed output
P
DC24VFeed output
Power supply mode
W
T
DC24Vpower supply
AC85-260VPower Supply (Switching Power Supply)
AC220VPower supply (linear power supply, can be omitted)
Note: The flashing alarm indicated by the flat LED has no communication.