Standard PROFIBUS-DP slave interface, compliant with IEC61158 TYPE3 PROFIBUS international standard and Chinese national standard GB/T 20540-2006;
● Baud rate adaptive 9600-12Mbps;
● Compatible with mainstream PROFIBUS master station equipment, such as Siemens 300/400 PLC, Beckhoff dp master station ABB 800F、 Omron main station, Hollysys LK PLC, Hollysys DCS, etc;
The CAN2.0A/2.0B interface complies with the CANopen CiA D raft Standard 301 standard;
Through the configuration and programming of the main station (PLC), CAN and CANopen protocol communication can be flexibly implemented;
Provide product GSD files for PROFIBUS network integration; The CAN communication baud rate can be selected through the main station configuration (such as in STEP7 configuration); 5K, 10K, 20K, 40K, 50K, 80K, 100K, 125K, 200K, 250K, 400K, 500K, 666K, 800K, with 'control word and status word' settings, can control the device's status in real time, meet user specific needs 1M optional.
Memory sharing gateway, the PROFIBUS master station reads/writes CANopen side station data directly based on the configured gateway PROFIBUS data area (I/Q area). The gateway GSD file is used for network integration, and CANopen configuration can be achieved through the main station configuration, providing the corresponding relationship between PROFIBUS I/Q and CANopen site data;
PB-B-CANopenGateway features
●PB-B-CANopenGateway divisionV10andV11Working mode.V10correctCANopenSlave mode,GSDThe file isDSCOS10.GSD.V11correctCANopenMaster station mode,GSDThe file isDSCOM11.GSD;
●Both types of gateways are equipped with status words, which can comprehensively reflect the gatewayCANopenCommunication status.
●PB-B-CANopenofV11Mode andPB-B-aCANofM1Similar patterns, need to be in placePROFIBUSMain station configuration (such asSTEP7)Medium configuration, gatewayCANopenCommand queue to be sent (various)TPDO、RPDO,SDO、SYNC、NMT、Heartbea t)And nodesIDThe gateway can send information such as interval, etcDynamically generate and (timed, triggered) send commands, and receive parsed slave station response commands and data.
●PB-B-CANO2Gateway onlyV21Working mode, done by gatewayCANopenThe main station,GSDThe file isDSCOM21.GSD.
●PB-B-CANO2gatewayV21Mode, also known as'Download configuration mode',gatewayCANopenThe relevant message parameters need to be configured in the upper level configuration software'Ding ShiCANOpenConfi ' Download to the bus bridge storage after configuration.V21Mode is more suitable as a user productPROFIBUSBatch matching of interface components, equivalent to user customizationPROFIBUSInterface module.
●PB-B-CANO2Gateway upper configuration software "DingshiCANOpenConfi”Featuring a user-friendly guidance interface, it guides the completion of the gatewayCANOPENMessage configuration of the main station.
●Both types of gateways are equipped with status words, which can comprehensively reflect the gatewayCANopenCommunication status.
CANopen gateway configuration software: CANOpenConfi
CANOpenConfi is a CANopen gateway configuration software developed and provided by Beijing Dingshi, with independent intellectual property rights.
CANOpenConfi has a user-friendly boot interface to guide the completion of message configuration for the gateway CANopen master station.
|
|
PB-B-aCANopen |
|
PROFIBUS parameters |
standard |
conform toIEC61158 TYPE3 PROFIBUSInternational standards, Chinese national standardsGB/T 20540-2006. |
|
speed |
Baud rate adaptive, 9200~12Mbps |
||
Data volume |
PROFIBUS input/output quantity can be freely set, maximum input/output: <3> Max Output Bytes ≤ 193 Bytes; 3> |
||
CAN interface parameters |
can protocol |
ISO11898-CiA301-CANopen |
|
physical interface |
Standard CAN driver interface isolation |
||
frame format |
Standard frame: 11 bit ID |
||
Master/Slave working mode |
V10mode:follow V11pattern:Master Dial switch setting |
||
Baud rate |
5K, 10K, 20K, 40K, 50K, 80K, 100K, 125K, 200K, 250K, 400K, 500K, 666K, 800K, 1Mbps optional |
||
Operational characteristics |
|||
collocation method |
● pass throughDPMain station configuration gateway
● M0The working mode needs to be inDPMain Station(STEP7)Configure the bus bridge in the middleCANCommunication parameters, such as baud rate, etc. ByDPMain Station(PLC/DCS)Programming to controlCANData transmission and reception, implementing free protocolsCANCount toPROFIBUSThe conversion.
● M1The working mode needs to be inDPMain Station(STEP7)Configure the bus bridge in the middleCANCommunication parameters, such as baud rate, are inserted by inserting different onesIO moduleAnd set different settingsIDNumber and receiving/sending length to be confirmedCANData transmission and reception. ● M1The mode can be configured at most24stripCANinstruction,Can be applied to eachCANMonitor the status of the equipment. |
||
GSD file | V10:DSCOS_10.GSDV11:DSCOS_11.GSD | ||
Electrical parameters |
power consumption |
Power supply: 24VDC (± 20%), current: 170mA (at 24VDC) |
|
authentication |
CE certification, PROFIBUS certification |
||
Temperature and humidity |
Working temperature: -20 ℃~+55 ℃ (for customers with lower temperature requirements, please make a purchasing statement); Transportation and storage: -40 ℃ to+70 ℃; Relative humidity at work: 5~95% (no condensation) |
||
installway |
Method: 35mm guide rail |
||
protection grade | IP20 | ||
weight | About 230g | ||
External dimensions | Dimensions: Width (70mm))×Length (112.5mm) × Thickness (39.5mm) | ||
Product Features |
Application scenarios |
<1> PB-B-CANopen1>For various purposesCANOPENProtocol device accessPROFIBUSBuses provide flexible and convenient solutions. <2> V102>、V11The mode is more suitable for system integration engineers, and configuration work needs to be completed in the main station configuration work, which requires simplePLCProgramming implementationCANOPENThe Lord/From the agreement. |
Outline and Device Layout of PROFIBUS Bus Bridge
Outline dimensions and installation of PROFIBUS bus bridge
Industry Applications
Wind power industry: Inner Mongolia wind farm, Zhangbei wind farm
Port Machinery: Sany Heavy Industry
Coal mining industry: Yangquan Coal Mine
Metallurgical industry: industrial furnace equipment
Plastic Machinery: Hangzhou in HeshunBOPETApplication in film production line
Products case
![]() |
Project Name:Stage mechanical control system of a certain theaterUsing the product:PB-B-CANopen Connecting products:The main station adopts SiemensS7300On site, we received SchneiderATV71Frequency converter. Effect analysis:The monitoring of the frequency converter in the stage machinery control system is very important, but currently, the communication interface of the frequency converter is mostly adopted internationallyCANopenCommunication protocol,CANopenIt has the advantages of anti-interference and good real-time performance. For the main control network, it isPROFIBUSAs for the control system, it faces the challenge ofCANopenProtocol conversion toPROFIBUSThe issue with the agreement. Adopting DingshiPB-B-CANopenConveniently applyPROFIBUSgiveCANopenConnect the equipment to provide real-time, safe, and reliable operation assurance for the stage machinery. It has the advantages of fast processing speed, large system resource margin, strong communication capability, and more stable and reliable performance. |
![]() |
Project Name:In a plastic industry company in Hangzhou2Application of Bi directional Stretching Polyester Film Production Line.Using the product:PB-B-CANopen Connecting products:The main station isS7-300 PLC,CANopenFrom station to stationLenze 9400Series servo drive Implementation function:Realize speed control of the entire production line Effect analysis:By selectingCANopenInterface, realizing the connection of multiple interfaces, while greatly reducing costs, the system runs stably and well. |
PB-B-CANOpen_Slave Product and Application Manual
PB-B-CANOpen_master Product and Application Manual
PB-B-CANOPEN GSD file
CANOPEN to PROFIBUS bus bridge version description