Beijing Kangansen Instrument Technology Co., Ltd
Home>Products>NIVELCO Capacitive Level Gauge
Product Groups
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
  • Address
    2-1702, Beichen New Era Building, No. 13 Beiyuan Road, Chaoyang District, Beijing
Contact Now
NIVELCO Capacitive Level Gauge
NIVELCO capacitance level gauge (capacitance level gauge) is a measuring instrument that uses changes in capacitance to measure the level of dielectri
Product details
  • NIVELCOProduct features of capacitive level gauge:
    The hard rod or steel cable probe can be extended up to 20m
    There are various forms of electrical levels that are widely used
    ● No movable parts
    ● Adopting intrinsic safety design
    ● Optional HART communication protocol

NIVELCOThe parameters of the capacitive level gauge are as follows:

type
Stick
Steel cable type
Heavy duty steel cable type
range
0.2 ~ 3m
1 ~ 20m
Wetware
material
Process connection
Stainless steel (DIN1.4517)
Probe section
Partial or complete PFA coated steel
Partially or completely FEP coated steel cables
Partial or complete PE coated steel cable
Shell material
Aluminum or plastic (VALOX412)
medium temperature
-30℃ ~ +200℃
-25℃ ~ +80℃
Medium pressure
Max. 6 MPa (60 bar)+20 ℃ (see pressure chart)
Max 1.6 MPa (16 bar)
ambient temperature
-26oC ~ +70oC
mechanical strength
-
7.7kN
45kN
Insulated electrode capacitor
-600pF/m
-200pF/m
-600pF/m
output
4 ~ 20mA, Two line system (3.9~20.5)
Output voltage/current
Resistors for measuring voltage: 1v/1mA
digital communication

HART

Display module (optional)
SAP-202
measuring range
0pF ~ 5nF
Minimum transmission range of capacitor
10pF or 10%
Damping time
3S, 10S or 60S
fault indication
COM and LED flash and output current changes to 3.8 or 22mA
Transmission voltage/power
12 ~ 36V Dcmax.22mA/48 ~ 800mW
Maximum Load
Rtmax=(ut-12v)/ 0.02A
accuracy
± 0.3%
Zero temperature drift
± 0.02%/oc
Electrical connection
Cable specifications: PG 16 or M20 x 1.5 Explosion proof cable: 8 15 mm, or . 6 ... 12 mm,
Cross wiring section: 9,5... . 10 mm wiring area n0.5... 1.5 mm2
Process connection
1”,11/2”Or BSP
11/2”NPT or BSP
Protection level
IP67
explosion-proof
grade
Standard type
Class III
Ex form
Explosion proof mark: II 1G EEx ia IIB T6
weight
2.3kg/0.5m probe
1.9kg/3m probe
4.5kg/3m probe
Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!

Successful operation!