VIP member
Large scale refrigerated air dryer
Large scale refrigerated air dryer
Product details


Water cooling type specification table
| model | CRX2900A-W | CRX4100A-WE | CRX5300A-WE | CRX7400A-WE | ||
| Handling air conditions | Handling air volume | ㎥ /min | 29 | 41 | 53 | 74 |
| Inlet air pressure | MPa | 0.69 | ||||
| Inlet air temperature | ℃ | 45 | ||||
| Dew point under export pressure | ℃ | 10 | ||||
| cooling water temperature | ℃ | 32 | ||||
| cooling water flow | ㎥ /h | 4.8 | 5.2 | 5.4 | 9.0 | |
| ambient temperature | ℃ | — | ||||
| Scope of application | Inlet air temperature | ℃ | 10 to 60 | |||
| ambient temperature | ℃ | 2 to 45 | ||||
| Use air pressure | MPa | 0.29 to 0.98 | ||||
| Cooling water temperature (water-cooled) | ℃ | 2 to 34 | ||||
| Cooling water pressure (gauge pressure) | MPa | 0.3 to 0.7 | ||||
| Dimensions (length x width x height) | mm | 1000×802×1500 | 1000×802×1500 | 1199×850×1500 | 1654×877×1620 | |
| Weight | kg | 278 | 350 | 395 | 495 | |
| automatic drain | Model number | AD5 (disc type) | ||||
| Diameter of drainage outlet | Rc1/2 | |||||
| Diameter of air piping (flange) | 2½B(65A) | 3B(80A) | 4B(100A) | |||
| Dual-Drive | Capacity control function | — | ○ | |||
| Energy saving effect during capacity control | — | 46% | ||||
| Refrigerant | R407C | R410A | ||||
| Electrical Characteristics | input power | V | 3-phase 380V ± 10% | |||
| power consumption | kW | 4.2 | 6.8 | 9.5 | 12.5 | |
| current value | A | 8.0 | 12.5 | 17.5 | 21.0 | |
| Pre set filter (set on CRX front-end/sold separately) | DSF2900A-SUS | DSF4100A-SUS | DSF5300A-SUS | DSF6100A-SUS, DSF8000A-SUS | ||
Specification table for air-cooled type
| model | CRX2300A | CRX3100A-E | CRX3500A-E | ||
| Handling air conditions | Handling air volume | ㎥ /min | 23 | 31 | 35 |
| Inlet air pressure | MPa | 0.69 | |||
| Inlet air temperature | ℃ | 50 | |||
| Dew point under export pressure | ℃ | 10 | |||
| cooling water temperature | ℃ | — | |||
| cooling water flow | ㎥ /h | — | |||
| ambient temperature | ℃ | 35 | |||
| Scope of application | Inlet air temperature | ℃ | 10 to 60 | ||
| ambient temperature | ℃ | 2 to 45 | |||
| Use air pressure | MPa | 0.29 to 0.98 | |||
| Cooling water temperature (water-cooled) | ℃ | — | |||
| Cooling water pressure (gauge pressure) | MPa | — | |||
| Dimensions (length x width x height) | mm | 1500×802×1500 | |||
| Weight | kg | 323 | 385 | 380 | |
| automatic drain | Model number | AD5 (disc type) | |||
| Diameter of drainage outlet | Rc1/2 | ||||
| Diameter of air piping (flange) | 2½B(65A) | 3B(80A) | 3B(80A) | ||
| Dual-Drive | Capacity control function | — | ○ | ○ | |
| Energy saving effect during capacity control | — | 46% | |||
| Refrigerant | R407C | ||||
| Electrical Characteristics | input power | V | 3-phase 380V ± 10% | ||
| power consumption | kW | 5.6 | 10.0 | 10.0 | |
| current value | A | 10.5 | 18.0 | 18.0 | |
| Pre set filter (set on CRX front-end/sold separately) | DSF2900A-SUS | DSF3500A-SUS | |||
The displayed value of air volume processing is based on ANR and converted to "32 ℃ · 75% RH at atmospheric pressure"
For detailed specifications, please refer to the specification sheet.
Please make sure to install a Super Droplet Filter (DSF) at the front end of the air piping for CRX.
Product features

System combination case

Catalog Download
Online inquiry