Product Description:KF-6901EMulti functional partial discharge diagnostic inspection instrumentEquipped with two detection modes: inspection mode、Diagnostic mode;Can be used for switchgeartransformerPerform partial discharge testing and positioning on equipment such as cable trays, cable joints, and insulators of overhead lines, as well as pole mounted switches; High frequency current(HFCT)The detection mode can perform partial discharge detection on transformers and cables; Ultra-high frequency(UHF)Contact ultrasonic waves(AE)The detection mode can be used forGISPerform partial discharge testing on the equipment. The detection results display discharge intensity, discharge phase, historical data, etc. in numerical and graphical formAnd alsoAnalyze the types of diagnostic signals and fault types, generate test reports and diagnostic results.at the same timehaveRFID data storage chip recognition and intelligent inspection function.
Functional Features
1. It integrates five principles of transient earth voltage (TEV) detection, ultra-high frequency (UHF) detection, ultrasonic (AE) detection, ultrasonic (AA) detection, and high-frequency current (HFCT) detection, and is suitable for partial discharge testing of high-voltage equipment.
2.Can meetGIS、 Partial discharge inspection and fault analysis and diagnosis of high-voltage equipment such as switchgear, transformers, and cables.
3.Fault data collection adopts wireless technology/There are two optional wired transmission methods, which facilitate on-site operation by personnel and ensure the safety of testing personnel. The sensor is fixed on site, and personnel can stay away from the tested equipment for testing.
4.The five testing principles all have amplitude detection, column trend chart, cycle chart detection, waveform chart detection, pulse chart detectionVarious methods such as PRPD and PRPS spectrum detectionchartAnalyze functions, diagnose signal types and fault types, generate test reports and diagnostic results. The instrument is compact, easy to carry, and versatile, which can truly improve the work efficiency of on-site users and reduce work intensity.
5 The instrument host adopts the Android system and is equipped with a quick inspection industrial control system (optional, capable of quick inspection). The system has a data saving function and can store all data including partial discharge test data, partial discharge test spectra, etc. in real time in the partial discharge tester host. The partial discharge detection data includes:TEV test data, ultrasonic test data, ultra-high frequency test data, and high-frequency current test data. Partial discharge testing spectra include pulse spectra, waveform spectra, cycle spectra, PRPD/PRPS spectra detection, etc.
6.The host is equipped with dedicated testing software, which has real-time control measurement and historical event analysis and playback functions. A data analysis software that complies with national standards, capable of storing, managing, and analyzing detection data, compatible with and importing partial discharge data files from other manufacturers that comply with national standards, and replaying them.
7.It has multiple synchronization functions to keep the phase detected by the periodic spectrum consistent with the frequency of the on-site power frequency.
8.haveRFID data storage chip recognition and intelligent inspection function.
1.1 Hardware parameters
1.1.1TEVTransient ground voltage measurement
uSensor: Capacitive
uMeasurement range:0~60dBmV
uFrequency range:1~100MHz
uresolving power:1dB
uAccuracy:±1dB
uMaximum pulse/Number of cycles:1400
uMinimum pulse rate:10Hz
1.1.2AAAir based ultrasonic measurement
uMeasurement range:-7dBuV~68dBuV
uresolving power:1dB
uAccuracy:±1dB
uSensor sensitivity:-65dB(0dB=1volt/ubarValid valueSPL)
uSensor center frequency:40kHz
uFrequency range:20~100kHz
uSensor diameter:16mm
uHeterodyne frequency:38.4kHz
uContact type air ultrasonic center frequency:20~300KHz
1.1.3AEContact ultrasonic measurement
uMeasurement range:0dBuV~68dBuV(0.001mv~1.000mv)
uresolving power:1dB
uAccuracy:±1dB
uSensor sensitivity:-65 dB (0 dB=1 volt/μbarValid valueSPL)
uFrequency range:0~200 kHz
1.1.4HFCThigh frequencyelectricityflow measurement
uSensor:HFCT
uMeasurement range:0pC~25000pC
uSensitivity: not greater than50pC
uDetection frequency:200KHz~50MHz
uDetecting bandwidth:100MHz
uInner diameter:45mm
uOuter diameter:110 mm
uOutput impedance:50Ω
uOutput interface:BNCconnector
1.1.5UHFUltra high frequency measurement
uSensor:UHF
uMeasurement range:-65dBm ~0dBm/-10~60dBm
uSensitivity:>10mmequivalent height
uresolving power:±0.5dB
uFrequency response:300MHz~1500MHz
uOutput impedance:50Ω
uOutput interface:BNCtype
1.1.6Input and output interfaces
uLEMOExternal ultrasonic sensor input interface
uBNCexternalAESensor input interface
uBNCexternalHFCTSensor input interface
uBNCexternalUHFSensor input interface
u3.5mmStereo headphone jack
ustandardSDCard data storage interface
u2.1mmLow voltage direct current(18VDC)Charger interface
u1.3mmPower synchronization input interface
uUSBinterface
uRJ45Ethernet interface
1.1.7SDblock
ustandard configuration16G(support4GBAnd aboveSDblock)
1.1.8headset
u3.5mmStereo headphone jack,32ohm
1.1.9built-in power supply
uInternal battery: Lithium ion battery
uNormal working hours: approximately8hour
uBattery protection function: low voltage automatic shutdown
1.1.10Battery Charger
uRated voltage:90~264V AC
uFrequency:47~63Hz
uCharging voltage:12VDC
uFull charging time:12hour
uSize:85mm×50mm×30mm
uOperating temperature:0~40Celsius
uHumidity:20~85%Relative humidity, no condensation