Differential pressure range |
±3735 Pa |
Absolute pressure range |
356 - 1016 mm Hg |
accuracy |
± 2% ± 0.025Pa of reading |
resolution |
0.001 Pa |
storage |
26500 data with data download function |
Standard configuration |
Host, 4 No. 5 rechargeable nickel hydrogen batteries, multi country AC adapter, 46 cm pitot tube probe, 2 static pressure probes, 4.8-meter rubber tube, data download software, USB computer connection cable, NIST calibration certificate and user manual |
800187 |
Airflow probe, 46cm, pitot tube. Range: 0.125-25 m/s, accuracy: ± 3% ± 0.04 m/s of reading (>0.25 m/s) |
800218 |
Temperature probe. Range: 4.4-60 ° C, accuracy: ± 0.3 ° C |
800219 |
Temperature and humidity probe. Range: -10-60 ° C/5-95%, Accuracy: ± 0.3 ° C/± 3% RH |
800909 |
16 point matrix probe. Range: 0.125-12.5 m/s, accuracy: ± 3% ± 0.04 m/s of reading (>0.25 m/s) |
960 |
Hot wire wind speed probe, capable of measuring temperature and wind speed. Range: 0-50 m/s; -18-93 ℃, accuracy: ± 3% of the reading or ± 0.015 m/s, whichever is greater; ± 0.3℃ |
962 |
Hot wire wind speed probe, capable of measuring temperature and wind speed, with a bendable probe. Range: 0-50 m/s; -18-93 ℃, accuracy: ± 3% of the reading or ± 0.015 m/s, whichever is greater; ± 0.3℃ |
964 |
Hot wire wind speed probe, capable of measuring temperature, humidity, and wind speed. Range: 0-50 m/s; -10 - 60℃; 0 - 95% Accuracy reading of ± 3% or ± 0.015 m/s, whichever is greater; ± 0.3℃; ± 3%RH |
966 |
Hot wire wind speed probe, capable of measuring temperature, humidity, and wind speed, with a bendable probe. Range: 0-50 m/s; -10 - 60℃; 0-95%. Accuracy: ± 3% of the reading or ± 0.015 m/s, whichever is greater; ± 0.3℃; ± 3% RH. |
8394 |
Wireless Bluetooth printer |
Micro wind pressure gauge
Model: 8715
The miniature wind pressure gauge 8715 is the most advanced and effective product in the DP-CALC series. Its features and advantages include the ability to quickly measure the velocity matrix of surface average wind speed, automatic zeroing, fast and reliable measurement results, and accurate measurement even at low flow rates.
Application scenarios
Measurement of surface wind speed for exhaust cabinets and biomedical safety cabinets
Testing, adjustment, and balancing of HVAC systems
Energy saving research
Clean room testing
industrial hygiene study
Compliance inspection
Micro Wind Pressure Gauge TSI8715 Tags: TSI8715, TSI8715 Wind Pressure Gauge, TSI8715 USA, Agent TSI8715 Wind Pressure Gauge, TSI8715 Wind Pressure Gauge USA, Zhongyi Environmental Science Agent TSI8715 USA, TSI Digital Wind Pressure Gauge 8715 USA, Imported Digital Micro Wind Pressure Gauge 8715, Zhongyi Environmental Science Sales TSI8715 USA, Buy TSI8715 and Find a Regular Agent, tsi8715