GPR-S100 series self operated gas pressure regulating valve
※ Suitable for gas generator pressure regulating valve devices in long-distance natural gas pipeline distribution stations, urban gas pressure regulat
Product details

Product Features

※ High pressure differential stable operation, with a pressure drop ratio of up to 120:1

※ Small size, can be installed in any position, easy to maintain

※ Spring direct acting, safe and reliable, durable and long-lasting

※ Can be used as either a monitoring valve or a working valve for two functional options

※ Simple pressure setting, high adjustment accuracy, and wide flow range


Product parameters


Standard execution EN 334
nominal pressure CLass150 ~ CLass900 ( 2MPa - 15MPa)
Nominal size DN25 ~ DN50 (NPS 1〞 ~ NPS 2〞)
Connection method Flange ANSI B16.5 RF, RTJ
Design Temperature -29℃ ~ 60℃ ; - 46℃ ~ 60℃
Maximum inlet pressure 15MPa (can be lower than this value according to the flange grade)
Export pressure range 0.07MPa~4MPa
Accuracy level AC ≤± 1~15% (AC1~AC15) depends on the operating pressure range
Close pressure level SG ≤ 5~20% (SG5~SG20) depending on the operating pressure range
Flow range ≤ 4300m3/h
protection grade IP65
Main materials Main valve body cast steel A 216 WCB A 352 LCC
Commander shell cast steel
Internal components made of stainless steel, steel, and copper
Close the spring steel (X750, A276316)
Sealing material reinforced polytetrafluoroethylene, nitrile rubber, synthetic rubber


Working principle



As shown in the figure below, when downstream demand decreases, the pressure on the lower side of the diaphragm increases. This pressure overcomes the set pressure of the pressure regulating valve (set by the set spring). By linking the push rod assembly, rotating rod, and small shaft, the valve gasket is brought closer to the valve seat and the gas flow is reduced. On the contrary, when downstream demand increases, the pressure on the underside of the diaphragm decreases. The spring forces the push rod assembly to pull the valve gasket downwards, away from the valve seat, and increase the gas flow rate.


Product Structure Diagram



Product dimension diagram



Product Connection



Note: When using S100H/S100HM type pressure regulating valves, the B dimension in the table needs to be increased by 10mm.


Comparison Table of Pressure and Flow of Pressure Regulating Valve




Product ordering and selection



Selection of pressure regulating valve

Product Model Description

Other special configuration instructions

The external pressure connection size of S100M and S100HM is 1/4'FNPT thread, and it is recommended to use a φ 10 sleeve and stainless steel pipe.

Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!

Successful operation!