1、 Product Overview
European style cable distribution box is a cable engineering equipment widely used in power distribution network systems in recent years. Its main features are bidirectional opening of doors and the use of through wall sleeves as connecting busbars. It has the advantages of small length, clear cable arrangementThree core cables have significant advantages such as not requiring large-span crossings. The cable connectors used comply with DIN47636 standard. Generally, bolt fixed cable joints with a rated current of 630A are used.
2、 Model and meaning
3、 Normal usage conditions
Wind speed: equivalent to 34m/s (not greater than 700Pa);
Humidity: The average daily relative humidity should not exceed 95%, and the average monthly relative humidity should not exceed 95%;
Seismic resistance: horizontal acceleration not exceeding 0.4m/s, vertical acceleration not exceeding 0.15m/s;
Installation site inclination: not more than 3 °;
Installation environment: The surrounding air is not significantly polluted by corrosive, flammable gases, water vapor, etc., and there is no severe vibration at the installation site.
Note: If ordering this product exceeds the above conditions, please consult with our company.
4、 Main technical parameters
rated voltage
12KV
Rated current
630A
Rated frequency
50Hz
Rated thermal stability current
20kA/3s
Rated dynamic stability current (peak value)
50kA
power-frequency withstand voltage
45kA
Lightning impulse withstand voltage
105kV
uniteContact resistance
40μΩ
Conductor operating temperature
≤95℃
partial discharge
≤10pc/13kV
Moisture test
11kV/100h pass through
Applicable cable types
XLPE
Applicable cable cross-section
25℃~100℃
Applicable ambient temperature
-40℃~+50℃
Applicable altitude
≤3000m
5、 Order number description
6、 Distribution diagram of European cable distribution box
7、 Schematic diagram of European joint
8、 Ordering Notice
The parameters in this plan are the standard configuration provided by our company. If the customer has no specific requirements, the company will supply according to the standard configuration. If it exceeds the requirements of this plan, please explain separately.