instructions
The EP1000 electric pneumatic valve positioner is used in conjunction with a control penalty to convert the signal output by the regulator into a pneumatic signal that drives the regulating valve. It overcomes the friction between the packing box and the valve stem, overcomes the unbalanced force of the medium pressure difference on the regulating valve core, and improves the valve's operating speed. It can achieve range control (segment signal), change the valve's operating mode, and control various types of pneumatic actuators with non-standard operating pressure.
Technical Parameter
Basic error: ± 1% (single action) ± 2% (double action)
Return difference: 1% (single action) 2% (double action)
Dead zone: 0.4% (single action) 0.2% (double action)
Rated travel: 0- (10-100) mm 0- (50 ° -90 °) angular travel (angular travel)
Gas source pressure: 0.14-0.55MPa
Output pressure: 0.02-0.5MPa
Gas consumption: Single action: 450L/h Double action: 3600L/h
Input signal: 4-20mA DC 0-10mA.DC (divisible)
Output characteristics: Linear regular type: (equal percentage non-linear special type)
Environmental temperature:- 35-+80 ° C (intrinsic safety type is -20-+60 ° C)
Relative temperature: 5% -100%
Explosion proof type: explosion-proof type, intrinsic safety type, ordinary type
Input impedance: 4-20mADC/300 ± 10 Ω (at 20 ℃)
0-10mADC/1000 ± 30 Ω (at 20 ℃)
Air source interface: M10 × 1 connected copper pipe with a diameter of 6
Power interface: M22 × 1.5
Shell material: Aluminum alloy
Dimensions: 203 × 160 × 105 (mm)
Weight: 2.8kg
Example: EP1111d: Indicating a linear single action, equipped with pneumatic diaphragm input signal: 4-20mADC
Explosion proof locator with output pressure of 0.02-0.1MPa
1211i: indicates dual action, equipped with pneumatic piston type (cylinder type) input signal: 4-20mADC
Localized locator with output pressure of 0-0.5MPa