Jinhu Ouwang Technology Co., Ltd
Home>Products>ECA210A, ECA220A flange mounted differential pressure transmitter
ECA210A, ECA220A flange mounted differential pressure transmitter
Overview: ECA210A and ECA220A flange mounted differential pressure transmitters are used to measure liquid, gas, and vapor pressures and convert them
Product details

summary
ECA210AThe ECA220A flange mounted differential pressure transmitter is used to measure the pressure of liquids, gases, and vapors, and convert it into a 4-20mADC current signal output. ECA210A and ECA220 can also communicate with each other through the HART275 handheld controller for settings, monitoring, etc.

Functional specifications
output
2-wire system, 4-20mA DC output, digital communication, programmable linear or square root output mode, HART protocol loaded on 4-20mA DC signal.
supply voltage
10.5~42V DC (working state)
16.4~42V DC (digital communication)
16.4~30V DC (intrinsic safety type)
Load (when output signal codes are D and E)
0-1335 Ω working state
250-600 Ω digital communication
HART
Communication Distance
When using multi-core twisted pair cables, the maximum communication distance can reach 2km, and the communication distance varies depending on the cable type.
Damping time constant
The sum of damping time constants for amplifier components and membrane enclosures. The damping time constant of the amplifier components can be adjusted within the range of 0.2 to 64 seconds for ambient temperature
-40~85℃(-40~248°F)
-30-80 ℃ (-22-176 ° F) [with LCD meter head]
Liquid contact temperature
-40~120℃(-40~248°F)


Performance specifications
Reference accuracy for range adjustment
(including linearity, hysteresis, and repeatability starting from zero)
±0.1%
stability
± 0.1% range upper limit/12 months
Model and Specification Code Table
model
Specification code
Explanation
reference price
notes
ECA210A
 
Flange mounted differential pressure transmitter (flat diaphragm type)
 
 
Conveying signals
E
D
4~20mA, HART protocol digital communication
4~20mA
 
 
Measurement range
(Capsule)
M
H
1~100Kpa
5
~500Kpa
 
 
High voltage side
(Flange side)
Material of the liquid receiving part

S
H
T
Membrane box, other
SUS316 SUS316L
Hastelloy C-276 Hastelloy C
Tantalum
 
 
Flange specifications
J1
J2
A1
A2
P1
P2
D2
D4
G2
G4
JIS10K
JIS20K
ANSI 150
ANSI 300
JPI 150
JPI 300
DIN PN10/16
DIN PN25/40
GB PN10/16(GB9115.9-88)
GB PN10/16(GB9115.9-88)
 
 
Flange size/material
A
B
C
D
E
F
2-inch(50mm,DN50)/S25C
2-inch(50mm,DN50)/SUS304
2-inch(50mm,DN50)/SUS316
3-inch(80mm,DN80)/S25C
3-inch(80mm,DN80)/SUS304
3-inch(80mm,DN80)/SUS316
 
 
Low pressure side pipeline connection
0
1
2
With M20×1.5Process connector
belt
½NPTInternal thread process joint, 2 wiring ports
No process joint (on capacitive flange)
¼NPTInternal thread)
 
 
Flange bolt material
A
B
C
SCM435
SUS630
SUH660
 
 
install
9
Horizontal piping connection, high pressure on the left side
 
 
electrical interface
5
G½Internal screw, 2 wiring ports with blind plugs
 
 
Display header
D
E
N
Digital header
Digital header with setting button
(No header)
 
 
Additional selection code
 
/Additional specifications
 
 
Explosion proof method
d
Explosion proof BT4
 
 
i
Intrinsically safe CT6
 
 
Flange size: 3 inches (80mm, DN80)

Flange nominal diameter and specifications
ØD
ØC
Øg
Ød
t
bolt hole
quantity
diameter
JIS 10K
185(7.28)
150(5.91)
130(5.12)
90(3.54)
18(0.71)
8
19(0.75)
JIS 20K
200(7.87)
160(6.30)
130(5.12)
90(3.54)


Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!

Successful operation!