Product Overview:
The power industry often experiences fires caused by overheating of power cables and equipment, resulting in extensive cable burning and equipment damage that forces shutdowns, making it difficult to resume production in a short period of time and causing significant economic losses. Analyzing the accident, the direct causes of overheating and fire in electrical equipment are poor quality of cable intermediate joints, loose compression joints, excessive contact resistance, and long-term operation leading to overheating of cable heads and insulation burning. Therefore, wireless temperature monitoring of cable joint points is required.
LoRaWAN-BGTL10The cable temperature measuring device is a product independently developed by our company based onLoRaWANThe communication cable temperature measurement device has functions such as temperature detection, data reporting, and remote monitoring, and adoptsLoRaModulation technology, followingLoRaWANWireless transmission protocol, in conjunction withLoRaWANGateway usage enables remote monitoring or intelligent management.
Functional features:
Following standardsLoRaWANCommunication protocol;
Capable of collecting data such as temperature and status;
pass throughLoRaWANThe protocol reports data according to the reporting cycle to achieve remote monitoring or intelligent management;
Automatic adjustment of transmission power;
Automatic network access and intelligent frequency hopping;
Ultra long communication distance and fast network access speed;
Automatic crystal oscillator temperature compensation, stable and reliable communication;
Low power design, energy-saving and environmentally friendly.
performance parameter
Battery specifications:ER17335,3.6V,2100mAh
Static power consumption:<10uA
Dynamic power consumption: ≤125mA
Battery lifespan: ≥2Year (reporting interval)5Minutes)
Measurement resolution:0.01℃
Temperature measurement range:-25 ~ 125℃
Strap temperature resistance:200℃
Strap material: Flame retardant silicone+Gas rubber
Transmission Protocol: FollowLoRaWANwireless transmission protocol
Frequency range:CN470MHz/AS923MHz/EU868MHz
Receiving sensitivity:-146dBm @SF12 125kHz BW
Transmission power: ≥18dBm
Antenna interface: external antennaSMAN Female
Working principle diagram
Installment and use
precautions
1.When the cable temperature measuring device comes into contact with the high-voltage object being measured, the device (including antenna, etc.) should avoid contact with other objects other than the object being measured, and be effectively isolated to avoid danger;
2.The cable temperature measuring device has switch holes, is not waterproof, and has a built-in lithium battery. It should not be used in places with water to prevent danger and damage to the device.
3.Transportation and storage
The product should not be subjected to severe impact during transportation and unpacking, and should be transported and stored according to relevant regulations;
Inventory and storage should be stored on racks in their original packaging conditions, and the stacking height should not exceed8storey;
The storage location should be clean, and the ambient temperature should be0-40℃, relative humidity not exceeding85%And there should be no harmful substances in the air that can cause corrosion.